Plan Review Notes
Plan Review Notes For Permit 20040217
Permit Number 20040217
Review Stop P
Sequence Number 2
Notes
Date Text
2020-05-21 13:55:202ND REVIEW FBC-2017
 PERMIT 20040217
 5/21/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 1ST REVIEW BELOW WILL BE MARKED AS
 PASSED OR FAILED. SEE NOTESIN CAPS FOR FAILED COMMENTS.
  
 1) FAILED. SHT. A-1 - THE WIDTH OF THE SHOWER IN THE
 GUEST BATH ON THE FIRST FLOOR IS SHOWN AS 1' - 11 3/4
 INCHES WIDE. THE MINIMUM WIDTH IS 30 INCHES PER 2017
 FBC- RES. SEC.P2708.1. THE SHOWER CAN BE A MINIMUM OF
 25 INCHES IN WIDTH IF THE CROSS-SECTIONAL AREA IS NOT
 LESS THAN 1300 SQUARE INCHES. CLARIFY. PROVIDE A NOTE
 AT THE SHOWER TO INDICATE A MINIMUM 1300 SQ. IN.
 CROSS-SECTIONAL AREA.
  
 2) FAILED. SHT. A-1 - THE WIDTH OF THE SHOWER IN BATH
 #1 ON THE SECOND FLOOR IS SHOWN AS 2'-0" WIDE. THE
 MINIMUM WIDTH IS 30 INCHES PER 2017 FBC- RES.
 SEC.P2708.1. THE SHOWER CAN BE A MINIMUM OF 25 INCHES
 IN WIDTH IF THE CROSS-SECTIONAL AREA IS NOT LESS THAN
 1300 SQUARE INCHES. CLARIFY. PROVIDE A NOTE AT THE
 SHOWER TO INDICATE A MINIMUM 1300 SQ. IN.
 CROSS-SECTIONAL AREA.
  
 3) FAILED. THE WATER SHUTOFF VALVES FOR THE STACKED
 WASHER/DRYER UNIT SHALL BE PROVIDED WITH ACCESS PER
 2017 FBC-RES. SEC.2903.9.3. PROVIDE A NOTE FOR ACCESS
 ON THE PLUMBING PLANS.
  
 4) PASSED.
  
 5) PASSED.
  
 6) PASSED.
  
 7) PASSED.
  
 8) FAILED. SHT. P-1 - DETAIL #2 - AIR ARRESTORS SHALL
 BE INSTALLED ON THE WATER LINES AT THE WASHING MACHINE
 BOX. 2017 FBC-RES. SEC.P2903.5. THE DRAIN FOR THE
 WASHER DETAIL SHOWS UNIONS. ACCESS SHALL BE PROVIDED TO
 THESE CONNECTIONS OR THEY SHALL BE REMOVED.2017
 FBC-RES. SEC.P2704. PROVIDE NOTE FOR ACCESS TO UNIONS
 AND VALVES.
  
 9) FAILED. THE ELECTRIC PLANS SHOW THE TANKLESS WATER
 HEATER AS BEING ELECTRIC BUT SHT. P-1 SHOWS THE WATER
 HEATER AS BEING GAS. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE WATER HEATER IF IT IS GAS.WPB
 AMEND. TO FBC SEC. 107.2.1.THE REQUESTED SPECS FOR THE
 WATER HEATER NOT PROVIDED.
  
 10) FAILED. SUBMIT A WATER RISER FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.3.5.3.THE WATER RISER WAS PROVIDED BUT
 DOES NOT SHOW LOCATIONS DISHWASHER AND ICE MAKER WATER
 SUPPLY LINES, AND LOCATIONS OF AIR ARRESTORS AND
 BACKFLOW PREVENTERS- SECTIONS P2902.2, P2902.4, P2903.5
 FBC RES.
  
 11) PASSED.
  
 12) PASSED.
  
 13) PASSED.
  
 NEW COMMENT:
 1) P2- FIRST FLOOR DRAIN LINES: SHOW REQUIRED CLEANOUT
 LOCATION AT THE JMUNCTION OF THE BUILDING SANITARY
 DRAIN AND THE SANITARY SEWER- SECTION P3005.2.3 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  