2020-04-13 11:03:001) SHT. A-1 - THE WIDTH OF THE SHOWER IN THE GUEST BATH
 ON THE FIRST FLOOR IS SHOWN AS 1' - 11 3/4 INCHES WIDE.
 THE MINIMUM WIDTH IS 30 INCHES PER 2017 FBC- RES.
 SEC.P2708.1. THE SHOWER CAN BE A MINIMUM OF 25 INCHES
 IN WIDTH IF THE CROSS-SECTIONAL AREA IS NOT LESS THAN
 1300 SQUARE INCHES. CLARIFY.
 2) SHT. A-1 - THE WIDTH OF THE SHOWER IN BATH #1 ON THE
 SECOND FLOOR IS SHOWN AS 2'-0" WIDE. THE MINIMUM WIDTH
 IS 30 INCHES PER 2017 FBC- RES. SEC.P2708.1. THE SHOWER
 CAN BE A MINIMUM OF 25 INCHES IN WIDTH IF THE
 CROSS-SECTIONAL AREA IS NOT LESS THAN 1300 SQUARE
 INCHES. CLARIFY.
 3) THE WATER SHUTOFF VALVES FOR THE STACCKED
 WASHER/DRYER UNIT SHALL BE PROVIDED WITH ACCESS PER
 2017 FBC-RES. SEC.2903.9.3.
 4) SHOW THE INSIDE DIMENSIONS (L X W ) OF THE SHOWER IN
 THE MASTER BATH. COMPLY WITH 2017 FBC RES. SEC.P2708.1.
 5) THE WIDT OF THE SPACE FOR THE WATER CLOSET ON THE
 2ND FLOOR IS SHAOWN AS 1'- 8 1/2 INCHES. THE MINIMUM
 DISTANCE OF A WATER CLOSET FROM A WALL, VANITY,
 PARTITION, ETC. TO THE CENTERLINE OF THE WATER CLOSET
 IS 15 INCHES. 2017 FBC-RES. SEC.P2705.1 (5).
 6) SHOW THE FIXTURE CLEARANCES OF ALL THE WATER CLOSETS
 ON THE PLANS. COMPLY WITH 2017 FBC-RES. SEC.P2705.1
 (5).
 7) SHT. P-1 - DETAIL #1 - THE SHOWER PAN SHALL BE
 PITCHED 1/4 INCH PER FOOT TO THE DRAIN PERR 2017
 FBC-RES. SEC.P2709.1.
 8) SHT. P-1 - DETAIL #2 - AIR ARRESTORS SHALL BE
 INSTALLED ON THE WATER LINES AT THE WASHING MACHINE
 BOX. 2017 FBC-RES. SEC.P2903.5. THE DRAIN FOR THE
 WASHER DETAIL SHOWS UNIONS. ACCEESS SHALL BE PROVIDED
 TO THESE CONNECTIONS OR THEY SHALL BE REMOVED.2017
 FBC-RES. SEC.P2704.
 9) THE ELECTRIC PLANS SHOW THE TANKLESS WATER HEATER AS
 BEING ELECTRIC BUT SHT. P-1 SHOWS THE WATER HEATER AS
 BEING GAS. SHT.SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE WATER HEATER IF IT IS GAS.WPB AMEND. TO FBC SEC.
 107.2.1.
 10) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO FBC
 SEC. 107.3.5.3.
 11) SHT. P-1 - DETAIL #4 - CALLS OUT AN ELECTRIC
 TANKLESS WATER HEATER BUT THE DETAIL ALSO SHOWS GAS.
 CLARIFY.
 12) SHT. P-1 - THE SOIL STACK FOR THE FIRST FLOOR
 POWDER ROOM AND SECOND FLOOR BATH #2 DOES NOT MEET
 CODE. AS DRAWN, IT VIOLATES 2017 FBC-RES. SECS.P3108.4,
 P3109.2.
 13) THE STACK FOR THE FIRST FLOOR GUEST BATH AND 2ND
 FLOOR MASTER BATH DOES NOT MEET CODE. AS DRAWN, IT
 VIOLATES 2017 FBC-RES. SECS.P3108.4, P3109.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  