| 2020-04-13 11:03:00 | 1) SHT. A-1 - THE WIDTH OF THE SHOWER IN THE GUEST BATH |
| | ON THE FIRST FLOOR IS SHOWN AS 1' - 11 3/4 INCHES WIDE. |
| | THE MINIMUM WIDTH IS 30 INCHES PER 2017 FBC- RES. |
| | SEC.P2708.1. THE SHOWER CAN BE A MINIMUM OF 25 INCHES |
| | IN WIDTH IF THE CROSS-SECTIONAL AREA IS NOT LESS THAN |
| | 1300 SQUARE INCHES. CLARIFY. |
| | 2) SHT. A-1 - THE WIDTH OF THE SHOWER IN BATH #1 ON THE |
| | SECOND FLOOR IS SHOWN AS 2'-0" WIDE. THE MINIMUM WIDTH |
| | IS 30 INCHES PER 2017 FBC- RES. SEC.P2708.1. THE SHOWER |
| | CAN BE A MINIMUM OF 25 INCHES IN WIDTH IF THE |
| | CROSS-SECTIONAL AREA IS NOT LESS THAN 1300 SQUARE |
| | INCHES. CLARIFY. |
| | 3) THE WATER SHUTOFF VALVES FOR THE STACCKED |
| | WASHER/DRYER UNIT SHALL BE PROVIDED WITH ACCESS PER |
| | 2017 FBC-RES. SEC.2903.9.3. |
| | 4) SHOW THE INSIDE DIMENSIONS (L X W ) OF THE SHOWER IN |
| | THE MASTER BATH. COMPLY WITH 2017 FBC RES. SEC.P2708.1. |
| | 5) THE WIDT OF THE SPACE FOR THE WATER CLOSET ON THE |
| | 2ND FLOOR IS SHAOWN AS 1'- 8 1/2 INCHES. THE MINIMUM |
| | DISTANCE OF A WATER CLOSET FROM A WALL, VANITY, |
| | PARTITION, ETC. TO THE CENTERLINE OF THE WATER CLOSET |
| | IS 15 INCHES. 2017 FBC-RES. SEC.P2705.1 (5). |
| | 6) SHOW THE FIXTURE CLEARANCES OF ALL THE WATER CLOSETS |
| | ON THE PLANS. COMPLY WITH 2017 FBC-RES. SEC.P2705.1 |
| | (5). |
| | 7) SHT. P-1 - DETAIL #1 - THE SHOWER PAN SHALL BE |
| | PITCHED 1/4 INCH PER FOOT TO THE DRAIN PERR 2017 |
| | FBC-RES. SEC.P2709.1. |
| | 8) SHT. P-1 - DETAIL #2 - AIR ARRESTORS SHALL BE |
| | INSTALLED ON THE WATER LINES AT THE WASHING MACHINE |
| | BOX. 2017 FBC-RES. SEC.P2903.5. THE DRAIN FOR THE |
| | WASHER DETAIL SHOWS UNIONS. ACCEESS SHALL BE PROVIDED |
| | TO THESE CONNECTIONS OR THEY SHALL BE REMOVED.2017 |
| | FBC-RES. SEC.P2704. |
| | 9) THE ELECTRIC PLANS SHOW THE TANKLESS WATER HEATER AS |
| | BEING ELECTRIC BUT SHT. P-1 SHOWS THE WATER HEATER AS |
| | BEING GAS. SHT.SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE WATER HEATER IF IT IS GAS.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 10) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO FBC |
| | SEC. 107.3.5.3. |
| | 11) SHT. P-1 - DETAIL #4 - CALLS OUT AN ELECTRIC |
| | TANKLESS WATER HEATER BUT THE DETAIL ALSO SHOWS GAS. |
| | CLARIFY. |
| | 12) SHT. P-1 - THE SOIL STACK FOR THE FIRST FLOOR |
| | POWDER ROOM AND SECOND FLOOR BATH #2 DOES NOT MEET |
| | CODE. AS DRAWN, IT VIOLATES 2017 FBC-RES. SECS.P3108.4, |
| | P3109.2. |
| | 13) THE STACK FOR THE FIRST FLOOR GUEST BATH AND 2ND |
| | FLOOR MASTER BATH DOES NOT MEET CODE. AS DRAWN, IT |
| | VIOLATES 2017 FBC-RES. SECS.P3108.4, P3109.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |