| 2020-05-01 14:17:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE LEVEL OF ALTERATION ON PLAN. FBC EX 501.1 |
| | 2. PROVIDE COMPLIANCE WITH FBC ENERGY. FBC EC C101.4.1, |
| | R401.2 |
| | 3. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED (AND |
| | SEALED WHERE APPLICABLE) BY THE PERSON RESPONSIBLE FOR |
| | THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481 |
| | 4. THIS REVIEW IS A MASTER PERMIT FOR ALL BUILDINGS. |
| | WILL THE CLUBHOUSE BUILDING BE IDENTICAL? SHOULD THERE |
| | BE A SEPARATE PLAN FOR THAT BUILDING? PROVIDE |
| | CLARIFICATION. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |