Plan Review Notes
Plan Review Notes For Permit 20040212
Permit Number 20040212
Review Stop B
Sequence Number 1
Notes
Date Text
2020-04-30 14:47:38RENOVATIONS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 ROOFING PRODUCT APPROVALS.
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 EXTERIOR WINDOW AND DOOR PRODUCT APPROVALS.
 3) FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. SEE "A" AND "B" BELOW.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 4) SEPARATE PERMITS ARE REQUIRED FOR EXTERIOR CONCRETE
 WORK, PARKING RESTRIPE AND POOL.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved