| Notes |
| Date |
Text |
| 2020-04-16 11:03:24 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION IS DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT CALCULATIONS, DETAILS AND ANY OTHER DOCMENTS | | | NECESSARY TO SHOW THAT REDUCING THE OVERFLOW SCUPPERS | | | FROM 4" TO 3" WILL NOT REDUCE THE REQUIRED AMOUNT OF | | | RAIN WATER DISCHARGE FORM THE ROOF MORE THAN REQUIRED | | | BY CODE. FBC 107.2.1.2 | | | | | | 2) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | |
|