Plan Review Notes
Plan Review Notes For Permit 20040142
Permit Number 20040142
Review Stop P
Sequence Number 1
Notes
Date Text
2020-04-15 09:50:221ST REVIEW FBC-2017 PLUMBING
 PERMIT #20040142
 4/25/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODESECTION
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2 & P1: SHOW THE REQUIRED FIXTURE CLEARANCE
 FOR THE WATER CLOSETS IN THE MASTER BATH AND BED # 1
 BATH- FIGURE R307.1 FBC RES.
  
 2) P1: UPDATE THE FBC PLUMBING 2014 REFERENCE TO THE
 CURRENT 2017 FLORIDA BUILDING CODE- RESIDENTIAL SIXTH
 EDITION.
  
 3) PROVIDE A WATER HEATER EQUIPMENT SCHEDULE ON THE
 PLAN INDICATING MAKE AND MODEL, GALLON SIZE, AND
 EFFICENCY RATING- SECTION P2801.3 FBC RES & TABLE
 C404.2 FBC EC.
  
 4) P1: INDICATE THE TYPE OF SHOWER VALVES TO BE
 INSTALLED- SECTION P2708.4 FBC RES. PLEASE NOTE THAT
 ACCEPTABLE VALVE TYPES ARE PRESSURE-BALANCE,
 THERMOSTATIC-MIXING, OR COMBINATION
 PRESSURE-BALANCED/THERMOSTATIC-MIXING.
  
 5) P1: PROVIDE SHOWER RECEPTOR AND PAN INSTALLATION
 DETAILS- SEE SECTION P2709 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  