| 2020-04-14 15:38:25 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) SA SMOKE ALARM IN GARAGE PER CHECK LISTING FOR ALARM |
| | 110.3 USUALLY NOT PERMITTED IN THE GARAGE. |
| | |
| | 2) MASTER BEDROOM MISSING A SA FBC R314, AND CARBON |
| | MONOXIDE DETECTORS MISSING |
| | |
| | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER |
| | CODE. FBC R314.3, 315.1; FBC 107.2.1 |
| | |
| | PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES. FBC R315.1 |
| | |
| | 3) ARCFAULTS ARE NOW REQUIRED IN KITCHEN AND LAUNDRY |
| | AREAS |
| | |
| | ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS, |
| | LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING |
| | ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC |
| | RE3902.16 |
| | |
| | 4) GFCI PROTECTION NOW REQUIRED IN LAUNDRY ROOM |
| | OUTLETS. |
| | |
| | E3902.9 LAUNDRY AREAS. 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN LAUNDRY AREAS SHALL |
| | HAVE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION FOR |
| | PERSONNEL. [210.8(A)(9)] |
| | |
| | 5) INTERSYSTEM BONDING BRIDGE MISSING AT SERVICE |
| | |
| | PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | |
| | |