2020-04-14 15:38:25FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SA SMOKE ALARM IN GARAGE PER CHECK LISTING FOR ALARM
 110.3 USUALLY NOT PERMITTED IN THE GARAGE.
  
 2) MASTER BEDROOM MISSING A SA FBC R314, AND CARBON
 MONOXIDE DETECTORS MISSING
  
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. FBC R314.3, 315.1; FBC 107.2.1
  
 PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES. FBC R315.1
  
 3) ARCFAULTS ARE NOW REQUIRED IN KITCHEN AND LAUNDRY
 AREAS
  
 ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS,
 LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING
 ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.16
  
 4) GFCI PROTECTION NOW REQUIRED IN LAUNDRY ROOM
 OUTLETS.
  
 E3902.9 LAUNDRY AREAS. 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION FOR
 PERSONNEL. [210.8(A)(9)]
  
 5) INTERSYSTEM BONDING BRIDGE MISSING AT SERVICE
  
 PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
  
  