| Plan Review Notes For Permit 20040142 |
| Permit Number |
20040142 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-04-14 09:39:54 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1. FBC B 107.2.1, PLEASE CORRECT THE INFORMATION FOUND | | | ON PAGES 002, 1 (DESIGN CRITERIA) AND 004, 3 (DESIGN | | | PARAMETERS). THE REFERENCED BUILDING CODE SHOULD BE THE | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION AND THE DESIGN | | | WIND EXPOSURE SHOULD BE "C". | | | | | | 2. FBC B 107.2, PLEASE PROVIDE THE MISSING DETAIL FOR | | | THE INTERIOR BEARING WALL INDICATED ON PAGE 006, 5.1 | | | ROOF FRAMING PLAN. | | | | | | 3. FBC B 107, PLEASE PROVIDE THE MISSING ENERGY | | | CALCULATIONS. | | | | | | 4. FBC B 107, PLEASE PROVIDE THE MISSING PRODUCT | | | APPROVALS FOR ROOFING MATERIALS, WINDOWS, AND DOORS. |
|