| 2020-04-15 10:00:47 | CHANGE OF OCCUPANCY |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE SHOW THE OCCUPANCY CLASSIFICATION PER FBC |
| | CHAPTER 3. |
| | 2) PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING MEANS OF |
| | EGRESS FBC CHAPTER10, FIRE SPRINKLERS FBC 420.5, FIRE |
| | ALARMS AND SMOKE ALARMS FBC 420.6 ETC. |
| | 3) PLEASE SHOW THE NUMBER OF OCCUPANTS. |
| | 4) PLEASE SHOW THE FIRE RATING OF THE SEPARATION WALLS |
| | TO COMPLY WITH FBC 420.2 |
| | 5) PLEASE DESCRIBE THE USE FOR THE BUILDING - WHAT ARE |
| | THE OCCUPANTS THERE FOR? |
| | |
| | GROUP R-4 OCCUPANCIES SHALL MEET THE REQUIREMENTS FOR |
| | CONSTRUCTION AS DEFINED FOR GROUP R-3, EXCEPT AS |
| | OTHERWISE PROVIDED FOR IN THIS CODE OR SHALL COMPLY |
| | WITH THE FLORIDA BUILDING CODE, RESIDENTIAL PROVIDED |
| | THE BUILDING IS PROTECTED BY AN AUTOMATIC SPRINKLER |
| | SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.2.8. |
| | |
| | 310.6.1CONDITION 1. |
| | THIS OCCUPANCY CONDITION SHALL INCLUDE BUILDINGS IN |
| | WHICH ALL PERSONS RECEIVING CUSTODIAL CARE, WITHOUT ANY |
| | ASSISTANCE, ARE CAPABLE OF RESPONDING TO AN EMERGENCY |
| | SITUATION TO COMPLETE BUILDING EVACUATION. 310.6.2 |
| | CONDITION 2. THIS OCCUPANCY CONDITION SHALL INCLUDE |
| | BUILDINGS IN WHICH THERE ARE ANY PERSONS RECEIVING |
| | CUSTODIAL CARE WHO REQUIRE LIMITED VERBAL OR PHYSICAL |
| | ASSISTANCE WHILE RESPONDING TO AN EMERGENCY SITUATION |
| | TO COMPLETE BUILDING EVACUATION. |
| | |
| | 310.6.2CONDITION 2. |
| | THIS OCCUPANCY CONDITION SHALL INCLUDE BUILDINGS IN |
| | WHICH THERE ARE ANY PERSONS RECEIVING CUSTODIAL CARE |
| | WHO REQUIRE LIMITED VERBAL OR PHYSICAL ASSISTANCE WHILE |
| | RESPONDING TO AN EMERGENCY SITUATION TO COMPLETE |
| | BUILDING EVACUATION. |