2020-04-14 14:27:322017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040074
 ADD: 3520 WHITEHALL SUITE: 406
 CONT: TBD/ TO BE DETERMINED
 TEL: ????
 E-MAIL:??? CONTACT: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. APRIL 13TH/2020
 ACTION: DENIED
  
 1) PERMIT APPLICATION:
 1) ARCHITECTS: FL ADMIN CODE 61G16.003(1) ARCHITECTS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 1C)(2) CONTRACTOR THE DESIGNER OF PLANS. 107.3.4.3
 CERTIFICATION/ DESIGNER BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR TO BE LICENSED IN
 THE TRADE THAT THEY WILL BE CREATING THE PLANS TO BE
 SUBMITTED TO THE BUILDING DEPARTMENT.
  
 2) 2ND REQUEST. ) FLOOR PLAN NOTE # 3A) INDICATES
 LAMINATE FLOORING MOHAWK BOARDWALK LAMINATE. THE
 UNDERLAYMENT MOHAWK SILENT GUARD STC73 & IIC 71. PLEASE
 PROVIDE THE ACTUAL TEST REPORTS FOR THE FOLLOWING:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL , LAMINATE AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH ALL 3 REQUIREMENTS:
  
 2A) 2ND REQUEST) FBC-B 2017 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET
  
 2B) 2ND REQUEST. FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) 2ND REQUEST. THE SUBMITTED TESTIS FOR CRITICAL
 RADIANT FLUX FOR FLOOR COVERING SYSTEMS TESTED TO ASTM
 E648. PLEASE NOTE #3 . THE TEST WE ARE ASKING FOR IS
 FOR THE FLOOR INSULATION UNDER THE FINISH FLOOR
 PRODUCT, NOT FOR FLOOR FINISHES.
  
 FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. INSULATION
 INSTALLED BETWEEN A FINISHED FLOOR AND SOLID DECKING
 WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  