Plan Review Notes
Plan Review Notes For Permit 20040056
Permit Number 20040056
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-04-08 14:52:12PERMIT #20040056
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1.SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 2.?FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH.
  
 3.THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 ANY FIRE ALARM SYSTEM EQUIPMENT FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRE AN EVALUATION OF THE EXISTING EQUIPMENT.
  