| Plan Review Notes For Permit 20040036 |
| Permit Number |
20040036 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-05-26 12:19:45 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) REPEAT COMMENT. THE CHART ON THE ENGINEERED DRAWINGS | | | HAS A MAXIMUM WINDSPEED OF 163 MPH IN EXPOSURE D FOR | | | THIS GENERATOR. A 170 MPH WIND SPEED IS REQUIRED. THE | | | GENERATOR PAD ENGINEERING FOR THE 22 KW GENERAC | | | GENERATOR WEIGHING 466 LBS DOES MEET THE 170 MPH WIND | | | LOAD IN EXPOSURE D. THIS PROPERTY IS LOCATED IN | | | EXPOSURE D. FBC-R301.2 |
|