| 2020-04-11 09:21:36 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E-1 |
| | |
| | 1) OUTLET NNEDED BY FRONT OF THE HOUSE. |
| | |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL |
| | |
| | PAGE E-2 |
| | |
| | 2) ROOM SHOWING NO WORK MISSING OUTLETS. |
| | |
| | E3901.2.1 SPACING. |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| | SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE |
| | OUTLET. [210.52(A)(1) |
| | |
| | PAGE E-5 |
| | |
| | 3) NOTES ON PAGE |
| | |
| | #2 ADD KITCHEN AND LAUNDRY TO AREAS SERVED BY AFCI. |
| | #5 CHANGE TO 75% OF LAMPS. |
| | THERE IS NO NOTE FOR NM CABLE PLEASE ADD IF YOU ARE |
| | GOING TO ALLOW. |
| | |
| | 4) NEED AIC RATING FOR SERVICE CAN BE A NOTE TO THE |
| | ELECTRICAL CONTRACTOR TO SUPPLY BY FINAL. |
| | |
| | E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. SERVICE |
| | EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM FAULT |
| | CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT NOT LESS |
| | THAN 10,000 AMPERES. (110.9) |
| | |
| | 5) PANEL AT MAIN HOUSE NEEDS A GROUNDING ELECTRODE |
| | SYSTEM INSTALLED. |
| | |
| | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) |
| | OR BRANCH CIRCUIT(S) (A) GROUNDING ELECTRODE. |
| | BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR |
| | BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE |
| | OR GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE |
| | WI TH PART III OF ARTICLE 250. THE GROUNDING ELECTRODE |
| | CONDUCTOR(S) SHALL BE CON NECTED IN ACCORDANCE WITH |
| | 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING |
| | ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN |
| | 250.50 SHALL BE INSTALLED |
| | |