| Plan Review Notes For Permit 20040015 |
| Permit Number |
20040015 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-04-10 16:07:18 | SFR ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) WINDOWS MARKED "B" FOR THE 2ND FLOOR BEDROOM NEED TO | | | MEET EGRESS REQUIREMENTS PER FBC R310.1 | | | 2) DRAWING A-403 SHOWS WINDOWS TO BE REUSED - CANNOT | | | REUSE WINDOWS WITHOUT AN UPDATED PRODUCT APPROVAL - FBC | | | EXISTING BUILDING 602.2 | | | 3) STRUCTURAL DRAWINGS DO NOT SHOW IN "ADOBE" AS | | | ELECTRONICALLY SIGNED BY THE ENGINEER. | | | 4) YOU HAVE A PRODUCT APPROVAL FOR FIXED GLASS - PLEASE | | | SHOW THE LOCATION FOR THE FIXED GLASS ON THE DRAWINGS. | | | 5) GARDEN WALL NEEDS TO BE ON A SEPARATE BUILDING | | | PERMIT - PLEASE PROVIDE A NOTE ON THE DRAWING FOR SUCH | | | OR REMOVE IT FROM THE DRAWINGS. | | | 6) PLEASE PROVIDE A SIGNED AND SEALED COPY OF THE | | | SURVEY - NEEDS TO BE ELECTRONICALLY SIGNED BY THE | | | SURVEYOR TO BE USED IN ELECTRONIC PLAN REVIEW. | | | |
|