| 2020-04-02 09:04:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. GFCI PROTECTION IS REQUIRED FOR RECEPTACLE OUTLETS |
| | INSTALLED IN A SHED. PROVIDE CORRECTION. NEC 210.8 |
| | 2. PLAN STATES THAT ALL EQUIPMENT IS OPTIONAL AND |
| | LOCATIONS MAY VARY, PLEASE PROVIDE PLAN THAT SHOWS WHAT |
| | THE ACTUAL INSTALLATION WILL BE. WPB FBC 107.2.1 |
| | 3. PROVIDE DETAILS OF THE CIRCUIT THAT WILL FEED THIS |
| | SHED. WHERE IS IT FED FROM, WHERE IS THE DISCONNECT FOR |
| | SEPARATE STRUCTURES, ETC. WPB FBC 107.2.1; NEC 225.31, |
| | 225.32 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |