Plan Review Notes
Plan Review Notes For Permit 20031435
Permit Number 20031435
Review Stop P
Sequence Number 2
Notes
Date Text
2020-05-14 07:58:50REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20031435 140 MONROE DR
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 COMMENT #1: CORRECTED
 COMMENT #2: SECOND REQUEST
 A.(RE: HYDRAULIC CALCULATIONS; PER WPB FBC 107.2. 1 AND
 APSP-7-2013, INCLUDE THE HEAD LOSS FOR THE POOL HEATER
 AS WELL AS THE VALVES AND FITTINGS.) TO BE CLEAR AS
 REQUIRED BY WPB FBC 107.2. 1 AND APSP-7-2013,
 CALCULATIONS SHALL INCLUDE THE HEAD LOSS FOR THE POOL
 HEATER AS WELL AS THE VALVES AND FITTINGS.
 B.(ADDITIONALLY, ALL EQUIPMENT SUBMITTALS SHALL BE
 CLEAR, EASILY READ AND SHALL INCLUDE ALL PERTINENT
 TECHNICAL INFORMATION INCLUDING BUT NOT LIMITED TO
 HYDRAULIC FLOW AND HEAD LOSS.) TO BE CLEAR AS REQUIRED
 BY WPB FBC 107.2. 1 AND APSP-7-2013, EQUIPMENT
 SUBMITTALS SHALL
 1.INCLUDE HYDRAULIC FLOW AND HEAD LOSS
 2.BE EASILY READ
 3.INDICATE SELECTED MODEL NUMBER IF THERE IS MORE THAN
 ONE LISTED IN SUBMITTAL
  
 COMMENT #3: CORRECTED
  
  
 GAS COMMENTS: GAS PLAN AND PERMIT REQUIRED
 POOL HEATER IS GAS. A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS, APPLIANCE/
 EQUIPMENT SPECIFICATIONS AND GAS RISER THAT REFLECT THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC
 SEC. 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS REQUIREMENTS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  