Plan Review Notes
Plan Review Notes For Permit 20031395
Permit Number 20031395
Review Stop G
Sequence Number 3
Notes
Date Text
2020-05-06 08:05:02JERRY SMITH:
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 3RD REVIEW
  
 GAS COMMENTS: DENIED
 AS REQUIRED BY TIM LARGE, THE INFORMATION ON THE
 RESPONSE NARRATIVE WAS TO BE ON THE PLANS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 REGARDING THE SUBMITTED PLANS, THE FOLLOWING IS NOTED:
 1) NEW STOVE APPEARS TO HAVE A TOTAL GAS DEMAND OF
 77,600 BTUS, NOT 43,100 BTUS AS NOTED ON THE RISER
 DIAGRAMS. PER WPB FBC 107.2.1, CORRECT THE DRAWING. IT
 IS NOTED THAT TOTAL DEMAND FOR THE SYSTEM AT 260,000
 BTUS IS ADEQUATE BUT SHOULD REFLECT ACTUAL TOTAL BTU
 DEMAND. PER WPB FBC 107.2.1, CORRECT THE DRAWING.
 2) FBC FG TABLE 402.4(15) NOTED ON PLANS USED FOR
 SIZING CSST TUBING SHALL BE ADDRESSED AS FOLLOWS:
 A. METER IS FOR INLET PRESSURE LESS THAN 2 PSI/PRESSURE
 DROP 0.5 INCH W.C./SPECIFIC GRAVITY 0.60 AND IS NOT THE
 TABLE TO BE USED FOR SIZING THE CSST TUBING IN THE 2
 PSI SYSTEM. PER WPB FBC 107.2.1, PROVIDE CORRECT TABLE
 FOR THE CSST TUBING IN THE 2 PSI SYSTEM (PLEASE NOTE
 THAT PRESSURE DROP IN 2 PSI SYSTEMS IS IN PSI, NOT W.C.
 AND NEEDS TO BE CORRECTLY EXPRESSED ON THE PLANS).
 B. IS EXPRESSED IN EHD (EQUIVALENT HYDRAULIC DIAMETER)
 UNITS, NOT DIAMETER IN INCHES. SIZING ON THE PLANS FOR
 CSST TUBING IS ? INCH. PER WPB FBC 107.2.1, PROVIDE
 CORRECT EHD (EQUIVALENT HYDRAULIC DIAMETER) SIZE.
 3) FBC FG TABLE 402.4(2) NOTED AT THE METER IS FOR
 INLET PRESSURE LESS THAN 2 PSI/PRESSURE DROP 0.5 INCH
 W.C./SPECIFIC GRAVITY 0.60 AND IS NOT THE TABLE TO BE
 USED FOR SIZING THE GALVANIZED PIPING IN THE 2 PSI
 SYSTEM (PLEASE NOTE THAT PRESSURE DROP IN 2 PSI SYSTEMS
 IS IN PSI, NOT WC). PER WPB FBC 107.2.1, PROVIDE
 CORRECT TABLE FOR THE GALVANIZED PIPING IN THE 2 PSI
 SYSTEM (PLEASE NOTE THAT PRESSURE DROP IN 2 PSI SYSTEMS
 IS IN PSI, NOT W.C. AND NEEDS TO BE CORRECTLY EXPRESSED
 ON THE PLANS). TABLE 402.4(2) SHALL BE USED FOR SIZING
 GALVANIZED PIPING DOWNSTREAM OF THE MP REGULATOR AND
 SHALL BE INDICATED AS SUCH WHERE APPLICABLE ON THE
 PLANS. PLEASE NOTE; IF YOUR SYSTEM IS FOR THE HOUSE IS
 LESS THAN 2 PSI THEN IT NEEDS TO BE CLEARLY INDICATED
 ON THE PLANS. THERE IS CONFUSION AND CONFLICTION
 BETWEEN 003 P-ISOMETRIC AND 004 P-GAS ISOMETRIC.
 ADDITIONALLY IF THE SYSTEM IS LESS THAN 2 PSI THEN
 REGULATORS AT THE APPLIANCES SHOULD ONLY BE FURNISHED
 IF REQUIRED BY THE MANUFACTURER.
 4) PER WPB FBC 107.2.1, PROVIDE ON THE PLAN 003
 P-ISOMETRIC DRAWING STATING HOW THE WATER HEATER
 CONDENSATION LINE WILL BE HANDLED. REFER TO RESPONSE
 LETTER DATED 4/24/2020.
 5) PER WPB FBC 107.2.1, PROVIDE DETAIL (ELEVATION) FOR
 VENT TERMINALS. ARE THE VENT TERMINALS UNDER A ROOF?
 VERIFY ALL REQUIRED MINIMUM CLEARANCES AS REQUIRED BY
 FBC FG 503.8 (3) AND AS REQUIRED BY MANUFACTURER.
 MANUFACTURER?S INSTALLATION MANUAL WAS PREVIOUSLY
 REQUESTED BUT AS OF YET HAS NOT BEEN SUBMITTED. SEE HTT
 PS://WWW.AIRSOLUTIONS.CA/IMAGES/PRODUCTS/NAVIEN/PRODUCT
 S/NPE-SERIES/NAVIEN-NPE-INSTALLATION-MANUAL.PDF
 6) IS THE NEW STOVE AN EXACT REPLACEMENT FOR THE OLD
 STOVE? IF NOT, SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR THE PER FBC FG.304.1 USING ONE OF THE METHODS
 LISTED IN FBC FG 304.5
 7) IT IS NOTED THAT THERE ARE SEVERAL ISOMETRIC AND
 PLAN VIEW DRAWINGS WITH SOME REDUNDANCY AS WELL AS
 CONFLICTS ACROSS THEM. PLEASE BE SURE TO KEEP ALL
 INFORMATION ON ALL PLANS CONSISTENT TO AVOID CONFUSION
 AND FURTHER COMMENTS THAT COULD DELAY APPROVAL.
 8) ALL UPDATED INFORMATION SHALL BE INDICATED ON THE
 PLANS PER WPB FBC 107.2.1.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER IN
 ACCORDANCE WITH FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  