| 2020-03-31 11:40:01 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT #20031395 |
| | 3/31/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | PLEASE NOTE THAT ALL GAS PIPING AND APPLIANCES EITHER |
| | INSTALLED UNDER THE EXPIRED PERMIT #09010132, OR ANY |
| | OTHER UNPERMITTED GAS PIPING AND GAS APPLIANCE |
| | INSTALLATIONS MUST BE ACCOUNTED FOR UNDER THIS NEW GAS |
| | PERMIT. |
| | |
| | 1) THE GAS PIPING DRAWING IS INCOMPLETE AND MORE |
| | INFORMATION IS REQUIRED FOR A FULL REVIEW. PLEASE |
| | PROVIDE A CLEARLY DRAWN GAS PIPING ISOMETRIC DRAWING |
| | THAT SHOWS THE FOLLOWING LIST OF ITEMS: |
| | |
| | A) TYPES OF PIPING, PIPE DIAMETERS, THE MEASUREMENTS OF |
| | EACH CUT LENGTH OF PIPE, AND THE TOTAL DEVELOPED LENGTH |
| | OF THE PIPING FROM THE POINT OF DELIVERY AT THE METER |
| | TO THE MOST REMOTE OUTLET IN THE BUILDING- SECTION |
| | G2413.4.1 & G2413.4.2 FBC RES. |
| | |
| | B) BTUH LOADS OF THE NEW WATER HEATER, THE EXISTING |
| | STOVE, AND ANY OTHER EXISTING GAS-FIRED APPLIANCES OR |
| | EQUIPMENT. SHOW THE LOAD AT EACH APPLIANCE LOCATION AND |
| | THE TOTAL LOAD ON THE SYSTEM- SECTION G2413.3, |
| | G24113.4, AND TABLES G2413.4(1) THROUGH G2413.4(21) FBC |
| | RES. |
| | |
| | C) GAS DELIVERY PRESSURE (PSI) OF THE SYSTEM AT THE |
| | METER AND AT EACH STEPDOWN (MP) REGULATOR- SECTION |
| | G2413.2 & G2413.3 FBC RES. |
| | |
| | D) INDICATE WHICH SIZING TABLES WERE USED FOR THE |
| | GALVANIZED PIPING AND THE CSST. PLEASE INDICATE THE |
| | CORRESPONDING EHD (EQUIVALENT HYDRAULIC DIAMETER) OF |
| | THE CSST AS INDICATED IN THE PIPE SIZING TABLES AND IN |
| | ACCORDANCE WITH THE CSST MANUFACTURER'S SPECIFICATIONS- |
| | SEE TABLES G2413.4(1) THROUGH (21). |
| | |
| | E) SHOW THE REQUIRED UNIONS FOR THE RIGID PIPING WITHIN |
| | ONE FOOT OF THE MP REGULATORS- SECTION G2421.2(7) FBC |
| | RES. |
| | |
| | F) ADVISORY: PLEASE NOTE THAT THE REGULATOR FOR THE |
| | TANKLESS WATER HEATER MUST BE CAPABLE OF REDUCING THE |
| | PRESSURE DOWN TO 10.5 " WC PER THE SUBMITTED CUT SHEET. |
| | |
| | 2) SUBMIT A SEPARATE FLOOR PLAN DRAWING THAT SHOWS THE |
| | LOCATIONS OF ALL NEW AND EXISTING GAS-FIRED APPLIANCES |
| | ON THE SYSTEM- SECTION G2406.1 & G2406.2 FBC RES. SHOW |
| | THE GAS VENT AND AIR INLET DUCT RUNS THROUGH THE |
| | BUILDING AND THEIR TOTAL RUN LENGTHS FOR THE WATER |
| | HEATER TO THEIR EXTERIOR INLET AND OUTLET LOCATIONS. |
| | INDICATE THE TYPES AND SIZES OF VENT AND AIR INLET |
| | PIPINGS AND SUBMIT MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS FOR THE WATER HEATER AND THE PIPING- |
| | SECTION M2005.1 & G2408.1 FBC RES. |
| | |
| | 3) SHOW HOW ACCESS FOR SERVICE AND REPLACEMENT OF THE |
| | WEATER HEATER WILL BE PROVIDED, AND THE REQUIRED 30X30 |
| | " LEVEL WORKING SPACE FOR THE APPLIANCE- SECTION |
| | P2801.4 FBC RES. |
| | |
| | 4) INDICATE HOW CONDENSATE FOR THE TANKLESS WATER |
| | HAETER WILL BE PROPERLY DISCHARGED TO THE EXTERIOR OF |
| | THE BUILDING- M1411.3 FBC RES. |
| | |
| | 5) IF POSSIBLE PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR ALL |
| | UNPERMITED OR EXISTING GAS-FIRED APPLIANCES OR |
| | EQUIPMENT- SECTION G2408.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |