 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL REVIEW DENIED:
  
 1) FBC B 107, PROVIDE ALL HVAC DETAILS, AS PER HVAC
 NOTE ON PAGE A-7 OF SUBMITTED PLANS, INCLUDING
 EQUIPMENT (A/C HANDLER & CONDENSING UNIT), DUCT LAYOUT
 W/SIZES AND CFM COUNT, EXTERIOR UNIT ANCHORING DETAIL,
 AHRI SHEETS AND A/C CALCULATIONS.
  
 NOTE: A MECHANICAL SUB-PERMIT IS REQUIRED.