| Plan Review Notes For Permit 20031386 |
| Permit Number |
20031386 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-31 10:50:54 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW DENIED: | | | | | | 1) FBC B 107, PROVIDE ALL HVAC DETAILS, AS PER HVAC | | | NOTE ON PAGE A-7 OF SUBMITTED PLANS, INCLUDING | | | EQUIPMENT (A/C HANDLER & CONDENSING UNIT), DUCT LAYOUT | | | W/SIZES AND CFM COUNT, EXTERIOR UNIT ANCHORING DETAIL, | | | AHRI SHEETS AND A/C CALCULATIONS. | | | | | | NOTE: A MECHANICAL SUB-PERMIT IS REQUIRED. |
|