| 2020-08-07 17:14:31 | 4TH REVIEW FBC-2017 PLUMBING |
| | PERMIT #2001359 |
| | 8/7/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-1: THE DOOR TO THE WOMEN'S TOILET ROOM SHALL |
| | NOT SWING INTO THE CLEAR FLOOR SPACE OF THE LAVATORY |
| | PER SECTION 603.2.3 FBC ACC UNLESS THE DRAWING IS |
| | REVISED TO SHOW COMPLIANCE WITH EXCEPTION 2. |
| | |
| | 2) A-1: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS FOR THE URINAL- SECTION 605.3. |
| | |
| | 3) A-1: REFER TO SECTION AND FIGURE 605.2 AND SHOW THE |
| | RIM HEIGHT AND THE DEPTH OF THE ACCESSIBLE URINAL. |
| | |
| | 4) A-1: KNEE AND TOE CLEARANCES FOR THE LAVATORY SINK |
| | NOT SHOW- SECTIONS 606.2, 305 & 306. |
| | |
| | 5) A-1: REFER TO FIGURES 604.5.1 & 604.5.2 AND SHOW THE |
| | CORRECT LENGTHS AND SPACINGS OF THE GRAB BARS. |
| | |
| | 6) A-1: REFER TO FIGURE 604.7 FOR CORRECT POSITIONING |
| | OF THE TOILET PAPER DISPENSER. |
| | |
| | 7) A-1, TANKLESS WATER HEATER: A) SHOW THE LOCATION OF |
| | THE WATER HEATER ON THE PLAN AND INDICATE HOW ACCESS |
| | WILL BE PROVIDED- SECTION 501.4 FBC P. B) PROVIDE THE |
| | MAKE AND MODEL AND GPM FLOW CAPACITY- TABLE 604.3. C) |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 502.1. |
| | |
| | 8) ME1: THE PREVIOUS REVIEW COMMENTS REQUIRING TEMPERED |
| | WATER AT THE LAVATORIES WAS NOT ADDRESSED- REFER TO |
| | SECTIONS 416.5 & 607.1.2 FBC P: TEMPERED WATER MAY BE |
| | DELIVERED BY THE WATER HEATER IF THE UNIT IS EQUIPPED |
| | WITH A WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS |
| | TO ASSE 1070 AND SHALL LIMIT THE TEMPERED WATER TO A |
| | MAXIMUM OF 110 DEGREES F. OTHERWISE A SEPARATE DEVICE |
| | MEETING COMPLIANCE SHALL BE INSTALLED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |