2020-08-07 17:14:314TH REVIEW FBC-2017 PLUMBING
 PERMIT #2001359
 8/7/2020
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1: THE DOOR TO THE WOMEN'S TOILET ROOM SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACE OF THE LAVATORY
 PER SECTION 603.2.3 FBC ACC UNLESS THE DRAWING IS
 REVISED TO SHOW COMPLIANCE WITH EXCEPTION 2.
  
 2) A-1: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE URINAL- SECTION 605.3.
  
 3) A-1: REFER TO SECTION AND FIGURE 605.2 AND SHOW THE
 RIM HEIGHT AND THE DEPTH OF THE ACCESSIBLE URINAL.
  
 4) A-1: KNEE AND TOE CLEARANCES FOR THE LAVATORY SINK
 NOT SHOW- SECTIONS 606.2, 305 & 306.
  
 5) A-1: REFER TO FIGURES 604.5.1 & 604.5.2 AND SHOW THE
 CORRECT LENGTHS AND SPACINGS OF THE GRAB BARS.
  
 6) A-1: REFER TO FIGURE 604.7 FOR CORRECT POSITIONING
 OF THE TOILET PAPER DISPENSER.
  
 7) A-1, TANKLESS WATER HEATER: A) SHOW THE LOCATION OF
 THE WATER HEATER ON THE PLAN AND INDICATE HOW ACCESS
 WILL BE PROVIDED- SECTION 501.4 FBC P. B) PROVIDE THE
 MAKE AND MODEL AND GPM FLOW CAPACITY- TABLE 604.3. C)
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 502.1.
  
 8) ME1: THE PREVIOUS REVIEW COMMENTS REQUIRING TEMPERED
 WATER AT THE LAVATORIES WAS NOT ADDRESSED- REFER TO
 SECTIONS 416.5 & 607.1.2 FBC P: TEMPERED WATER MAY BE
 DELIVERED BY THE WATER HEATER IF THE UNIT IS EQUIPPED
 WITH A WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS
 TO ASSE 1070 AND SHALL LIMIT THE TEMPERED WATER TO A
 MAXIMUM OF 110 DEGREES F. OTHERWISE A SEPARATE DEVICE
 MEETING COMPLIANCE SHALL BE INSTALLED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  