Plan Review Notes
Plan Review Notes For Permit 20031359
Permit Number 20031359
Review Stop P
Sequence Number 3
Notes
Date Text
2020-07-09 11:29:36 
 3RD REVIEW FBC-2017 PLUMBING
 PERMIT #2001359
 5/12/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: THE PLAN SHOWS ONLY ONE OF THE TWO ALTERED
 TOILET ROOMS BEING MADE ACCESSIBLE. REFER TO SECTIONS
 202.3 AND 213.1 FBC ACC WHICH REQUIRES EACH ALTERED
 TOILET ROOM TO MEET COMPLIANCE. THE ARCHITECT OF RECORD
 HAS SUBMITTED A REQUEST BASED ON DISPROPORTIONATE COSTS
 TO PROVIDE ONLY ONE ACCESSIBLE UNISEX TOILET ROOM. THE
 PROPOSED PLANS, HOWEVER INDICATE DEMOLITION AND
 RECONSTRUCTION OF TWO TOILET ROOMS. BASED ON THE CODE
 SECTIONS LISTED ABOVE, EACH ALTERED TOILET ROOM SHALL
 BE MADE ACCESSIBLE. DISPROPORTIONAL COSTS TO PROVIDE
 ONE ACCESSIBLE TOILET ROOM WOULD NOT BE APPLICABLE IN
 THIS SPECIFIC CASE- SECTIONS 202.4.1 & 202.4.2 FBC ACC.
  
 2) SHEET A1: PLEASE PROVIDE ENLARGED DIMENSIONED
 DRAWINGS OF THE ALTERED TOILET ROOM WITH THE URINAL TO
 SHOW COMPLIANCE WITH SECTION 213.2 FBC ACC. THE
 ENLARGED DRAWINGS SHALL SHOW:
 A) CLEAR FLOOR SPACE FOR THE WATER CLOSET- SECTION
 604.3 FBC ACC.
 B) CLEAR FLOOR SPACE FOR THE LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER IN THE TOILET ROOM- SECTION
 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL OR
 PARTITION- SECTION 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 F) HEIGHT OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTIONS 604.5 AND 609.4
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 J) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
 K) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3
 3) A1: MISSING DETAILS FOR THE ENLARGED ACCESSIBLE
 TOILET ROOM DRAWING:
 A) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
 B) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3
 C) MOUNTING HEIGHTS OF GRAB BARS- SECTION 609.4
 D) MOUNTING HEIGHT OF THE TOILET PAPER DISPENSER-
 SECTION 604.7.
  
 3) A1: CONCERNING THE TOILET ROOM WITH THE URINAL
 PLEASE NOTE:
 A) THE URINAL SHALL NOT BE LOCATED IN THE REQUIRED
 CLEAR FLOOR SPACE OF THE WATER CLOSET- SECTION 604.3.2
 FBC ACC.
 B) THE WATER CLOSET SHALL OCCUPY A SEPARATE COMPARTMENT
 WITH WALLS OR PARTITIONS AND A DOOR. EXCEPTION: NOT
 REQUIRED IN A SINGLE-OCCUPANT TOILET ROOM WITH A
 LOCKABLE DOOR- SECTION 405.3.4 FBC P.
  
 4) A2: THE PREVIOUS REVIEW COMMENT #6 REQUIRING
 TEMPERED WATER AT THE LAVATORIES WAS NOT ADDRESSED-
 REFER TO SECTIONS 416.5 FBC P. REFER TO SECTION
 607.1.2: TEMPERED WATER SHALL BE SUPPLIED THROUGH A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 AND SHALL LIMIT THE TEMPERED WATER TO A MAXIMUM OF
 110 DEGREES F.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  