| 2020-05-12 13:49:48 | |
| | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT #2001359 |
| | 5/12/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW HAVE NOT BEEN ADDRESSED- |
| | PLEASE COMPLY. |
| | |
| | 1) SHEET A1: PLEASE PROVIDE ENLARGED DIMENSIONED |
| | DRAWINGS OF THE NEW MEN'S AND WOMEN'S TOILET ROOMS TO |
| | SHOW COMPLIANCE WITH SECTION 213.2 FBC ACC. THE |
| | ENLARGED DRAWINGS SHALL SHOW: |
| | A) CLEAR FLOOR SPACES FOR THE WATER CLOSETS- SECTION |
| | 604.3 FBC ACC. |
| | B) CLEAR FLOOR SPACES FOR THE LAVATORIES- SECTION |
| | 606.2. |
| | C) TURNING SPACES IN THE TOILET ROOMS- SECTION 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS |
| | OR PARTITIONS- SECTION 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5 |
| | G) LOCATIONS OF FLUSH CONTROLS- SECTION 604.6. |
| | H) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR |
| | DISPENSERS- SECTION 604.7 |
| | |
| | 2) A1, MENS TOILET ROOM |
| | A) THE URINAL SHALL NOT BE LOCATED IN THE REQUIRED |
| | CLEAR FLOOR SPACE OF THE WATER CLOSET- SECTION 604.3.2. |
| | B) THE WATER CLOSET SHALL OCCUPY A SEPARATE COMPARTMENT |
| | WITH WALLS OR PARTITIONS AND A DOOR. EXCEPTION: NOT |
| | REQUIRED IN A SINGLE-OCCUPANT TOILET ROOM WITH A |
| | LOCKABLE DOOR- SECTION 405.3.4 |
| | C) PROVIDE URINAL PARTITION DETAILS- SECTION 405.3.5 |
| | FBC P. |
| | |
| | 3) A1, WOMEN'S TOILET ROOM: THE WHEELCHAIR ACCESSIBLE |
| | TOILET COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY |
| | WITHIN IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17 |
| | INCHES DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE |
| | LAVATORY SHALL BE MOUNTED SO AS NOT TO OVERLAP THE |
| | CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION 604 FOR THE |
| | WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT AND SHALL |
| | COMPLY WITH SECTION 606. PLEASE NOTE THAT FLORIDA LAW, |
| | SECTION 553.504(5), F.S., STIPULATES THAT "...REQUIRED |
| | BATHING ROOMS AND TOILET ROOMS IN NEW CONSTRUCTION |
| | SHALL BE DESIGNED AND CONSTRUCTED..." WITH AN |
| | ACCESSIBLE LAVATORY IN THE WHEELCHAIR ACCESSIBLE |
| | COMPARTMENT AND THE WATER CLOSET LOCATED IN A CORNER |
| | DIAGONAL TO THE DOOR. |
| | |
| | 4) A1: PROVIDE A PLUMBING FIXTURE SCHEDULE ON THE PLAN- |
| | SECTIONS 416, 419, & 420 FBC P. |
| | |
| | 5) A1: THE URINAL CANNOT CONNECT TO THE HORIZONTAL WET |
| | VENT FOR THE TOILET FIXTURES AND SHALL BE INDIVIDUALLY |
| | VENTED- SECTION 912.1 FBC P. |
| | |
| | 6) A1: PROVIDE A WATER RISER DRAWING- SECTION 604.2 FBC |
| | P. THE RISER SHALL INDICATE PIPE SIZES, LOCATIONS OF |
| | SHUT OFF VALVES, MIXING VALVES ETC- SECTION 107.2.1 |
| | WPB. PLEASE NOTE THAT TEMPERED WATER SHALL BE PROVIDED |
| | TO THE LAVATORIES IN COMPLIANCE WITH SECTION 416.5 FBC |
| | P. |
| | |
| | 7) PROVIDE ARCHITECTURAL DETAILS FOR FLOOR AND WALL |
| | FINISHES IN THE NEW TOILET ROOMS- SECTION 405.2 FBC P |
| | AND 107.2.1 WPB |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |