2020-03-31 17:10:38 
 1ST REVIEW FBC-2017 PLUMBING
 PERMIT #2001359
 3/31/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: PLEASE PROVIDE ENLARGED DIMENSIONED
 DRAWINGS OF THE NEW MEN'S AND WOMEN'S TOILET ROOMS TO
 SHOW COMPLIANCE WITH SECTION 213.2 FBC ACC. THE
 ENLARGED DRAWINGS SHALL SHOW:
 A) CLEAR FLOOR SPACES FOR THE WATER CLOSETS- SECTION
 604.3 FBC ACC.
 B) CLEAR FLOOR SPACES FOR THE LAVATORIES- SECTION
 606.2.
 C) TURNING SPACES IN THE TOILET ROOMS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 G) LOCATIONS OF FLUSH CONTROLS- SECTION 604.6.
 H) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 DISPENSERS- SECTION 604.7
  
 2) A1, MENS TOILET ROOM
 A) THE URINAL SHALL NOT BE LOCATED IN THE REQUIRED
 CLEAR FLOOR SPACE OF THE WATER CLOSET- SECTION 604.3.2.
 B) THE WATER CLOSET SHALL OCCUPY A SEPARATE COMPARTMENT
 WITH WALLS OR PARTITIONS AND A DOOR. EXCEPTION: NOT
 REQUIRED IN A SINGLE-OCCUPANT TOILET ROOM WITH A
 LOCKABLE DOOR- SECTION 405.3.4
 C) PROVIDE URINAL PARTITION DETAILS- SECTION 405.3.5
 FBC P.
  
 3) A1, WOMEN'S TOILET ROOM: THE WHEELCHAIR ACCESSIBLE
 TOILET COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY
 WITHIN IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17
 INCHES DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE
 LAVATORY SHALL BE MOUNTED SO AS NOT TO OVERLAP THE
 CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION 604 FOR THE
 WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT AND SHALL
 COMPLY WITH SECTION 606. PLEASE NOTE THAT FLORIDA LAW,
 SECTION 553.504(5), F.S., STIPULATES THAT "...REQUIRED
 BATHING ROOMS AND TOILET ROOMS IN NEW CONSTRUCTION
 SHALL BE DESIGNED AND CONSTRUCTED..." WITH AN
 ACCESSIBLE LAVATORY IN THE WHEELCHAIR ACCESSIBLE
 COMPARTMENT AND THE WATER CLOSET LOCATED IN A CORNER
 DIAGONAL TO THE DOOR.
  
 4) A1: PROVIDE A PLUMBING FIXTURE SCHEDULE ON THE PLAN-
 SECTIONS 416, 419, & 420 FBC P.
  
 5) A1: THE URINAL CANNOT CONNECT TO THE HORIZONTAL WET
 VENT FOR THE TOILET FIXTURES AND SHALL BE INDIVIDUALLY
 VENTED- SECTION 912.1 FBC P.
  
 6) A1: PROVIDE A WATER RISER DRAWING- SECTION 604.2 FBC
 P. THE RISER SHALL INDICATE PIPE SIZES, LOCATIONS OF
 SHUT OFF VALVES, MIXING VALVES ETC- SECTION 107.2.1
 WPB. PLEASE NOTE THAT TEMPERED WATER SHALL BE PROVIDED
 TO THE LAVATORIES IN COMPLIANCE WITH SECTION 416.5 FBC
 P.
  
 7) PROVIDE ARCHITECTURAL DETAILS FOR FLOOR AND WALL
 FINISHES IN THE NEW TOILET ROOMS- SECTION 405.2 FBC P
 AND 107.2.1 WPB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  