| Plan Review Notes For Permit 20031328 |
| Permit Number |
20031328 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-04-21 09:55:44 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ON PRODUCT APPROVAL FL 477-R8 FOR THE FLAT ROOF, | | | SPECIFY THE SYSTEM NUMBER AND MAXIMUM DESIGN PRESSURE | | | ON THE APPROPRIATE ROOF CHART FOR A NON-INSULATED TORCH | | | APPLIED ROOF COVERING. THE MAXIMUM DESIGN ROOF PRESSURE | | | FOR THE SYSTEM WILL HAVE TO BE -90 PSF OR MORE. IF NOT | | | ENGINEERED FASTENER SPACING CALCULATIONS WILL BE | | | REQUIRED, IF ALLOWED BY THE PRODUCT APPROVAL. CLEARLY | | | MARK THE ITEMS THAT APPLY TO YOUR PROJECT ON THE | | | PRODUCT APPROVAL. FBC 107.2.1 | | | | | | |
|