Plan Review Notes
Plan Review Notes For Permit 20031328
Permit Number 20031328
Review Stop B
Sequence Number 2
Notes
Date Text
2020-04-21 09:55:44PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON PRODUCT APPROVAL FL 477-R8 FOR THE FLAT ROOF,
 SPECIFY THE SYSTEM NUMBER AND MAXIMUM DESIGN PRESSURE
 ON THE APPROPRIATE ROOF CHART FOR A NON-INSULATED TORCH
 APPLIED ROOF COVERING. THE MAXIMUM DESIGN ROOF PRESSURE
 FOR THE SYSTEM WILL HAVE TO BE -90 PSF OR MORE. IF NOT
 ENGINEERED FASTENER SPACING CALCULATIONS WILL BE
 REQUIRED, IF ALLOWED BY THE PRODUCT APPROVAL. CLEARLY
 MARK THE ITEMS THAT APPLY TO YOUR PROJECT ON THE
 PRODUCT APPROVAL. FBC 107.2.1
  
  