| Plan Review Notes For Permit 20031326 |
| Permit Number |
20031326 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-14 16:25:12 | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) DISCONNECT TO BE INSTALLED PER 600.6 (A) LOCATION. | | | (1) AT POINT OF ENTRY TO A SIGN ENCLOSURE. THE | | | DISCONNECT SHALL BE LOCATED AT THE POINT THE FEEDER | | | CIRCUIT OR BRANCH CIRCUIT(S) SUPPLYING A SIGN OR | | | OUTLINE LIGHTING SYSTEM ENTERS A SIGN ENCLOSURE OR A | | | POLE IN ACCORDANCE WITH 600.5(C)(3) AND SHALL | | | DISCONNECT ALL WIRING WHERE IT ENTERS THE ENCLOSURE OF | | | THE SIGN OR POLE |
|