Plan Review Notes
Plan Review Notes For Permit 20031326
Permit Number 20031326
Review Stop E
Sequence Number 1
Notes
Date Text
2020-05-14 16:25:12 
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) DISCONNECT TO BE INSTALLED PER 600.6 (A) LOCATION.
 (1) AT POINT OF ENTRY TO A SIGN ENCLOSURE. THE
 DISCONNECT SHALL BE LOCATED AT THE POINT THE FEEDER
 CIRCUIT OR BRANCH CIRCUIT(S) SUPPLYING A SIGN OR
 OUTLINE LIGHTING SYSTEM ENTERS A SIGN ENCLOSURE OR A
 POLE IN ACCORDANCE WITH 600.5(C)(3) AND SHALL
 DISCONNECT ALL WIRING WHERE IT ENTERS THE ENCLOSURE OF
 THE SIGN OR POLE