| 2020-05-14 16:58:36 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) VALUE FOR THIS SIGN IS LOW (25000) |
| | |
| | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 2) DISCONNECT TO BE INSTALLED PER 600.6 (A) LOCATION. |
| | (1) AT POINT OF ENTRY TO A SIGN ENCLOSURE. THE |
| | DISCONNECT SHALL BE LOCATED AT THE POINT THE FEEDER |
| | CIRCUIT OR BRANCH CIRCUIT(S) SUPPLYING A SIGN OR |
| | OUTLINE LIGHTING SYSTEM ENTERS A SIGN ENCLOSURE OR A |
| | POLE IN ACCORDANCE WITH 600.5(C)(3) AND SHALL |
| | DISCONNECT ALL WIRING WHERE IT ENTERS THE ENCLOSURE OF |
| | THE SIGN OR POLE. |
| | |
| | 3) LICENSE NUMBER MISSING FROM ELECTRICAL PERMIT AND |
| | ONLY ERS OR ECS ARE LICENSED TO MAKE THAT CONNECTION. |