| Plan Review Notes For Permit 20031307 |
| Permit Number |
20031307 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-07-24 09:57:10 | 3RD REVIEW FBC-2017 PLUMBING | | | PERMIT #20031307 | | | 7/24/2020 | | | | | | CODES IN EFFECT: | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE NEW PLUMBING PLAN MUST BEAR THE LICENSE NUMBER | | | AND SIGNATURE OF THE CONTRACTOR OR QUALIFIER WHO | | | PREPARED THE DRAWING- SECTION 107.2.1 WPB AND FL. | | | STATUTES 471.003(2)(H) & 471.025. | | | | | | 2) PREVIOUS REVIEW COMMENT NOT ADDRESSED: REFER TO | | | SECTIONS 409.2 & 608.3 FBC P- INDICATE ON THE PLANS HOW | | | THE WATER SUPPLY LINES TO THE DISHWASHER AND ICE MAKER | | | WILL BE PROTECTED AGAINST BACKFLOW. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|