| 2020-05-08 11:57:41 | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | PLAN REVIEW - ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER ? BUILDING - PX3169 |
| | PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE AIC RATING OF TRANSFORMER FROM POWER |
| | COMPANY. |
| | |
| | PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT FROM |
| | UTILITY. |
| | |
| | E3404.2 INTERRUPTING RATING. |
| | |
| | EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS |
| | SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 |
| | AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT |
| | LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN |
| | INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT |
| | LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9) |
| | |
| | AIC RATING OF SERVICE DISCONNECT AND PANEL |
| | FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. |
| | SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM |
| | FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT |
| | NOT LESS THAN 10,000 AMPERES. (110.9) |
| | |
| | |
| | 2. PROVIDE INTERSYSTEM BONDING CONNECTION AT SERVICE. |
| | |
| | PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | |
| | 3. PANEL SIZE CALCULATION FOR PANEL B USES INCORRECT |
| | KVA. TOTAL PANEL KVA IS 2.2 KVA. PANEL SIZE CALCULATION |
| | USES 18.7 KVA. |
| | |
| | PLEASE CORRECT. |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. HIGH EFFICACY LAMPS. |
| | |
| | PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". |
| | A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1 |
| | |
| | 5. OUTLET IN POWDER ROOM APPEARS TO EXCEED THE 36 INCH |
| | MINIMUM REQUIREMENT PER E3901.6. |
| | |
| | PLEASE VERIFY |
| | |
| | 6. OUTLETS FOR GARAGE DOOR OPENERS MISSING FROM PLAN. |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |