| 2020-08-07 16:40:18 | 8/5/2020 1ST GAS REVIEW **DENIED** WITH COMMENTS NOTE - |
| | A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | 1- I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND |
| | THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF |
| | ANY GAS AT THIS ADDRESS.SINCE THERE IS NO RECORD OF A |
| | PERMIT FOR THE GAS, THE EXISTING GAS LINES SHALL |
| | CONSIDERED AS NEW. WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 2 -SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES |
| | SECS. G2413.4.1, G2413.4.2. |
| | |
| | 3- TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4- SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| | 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| | |
| | 5- A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS |
| | TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE |
| | MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD, |
| | 2017 FBC FG SEC.G2408.1. |
| | |
| | 6- THERE ARE SECTIONS OF PRINTING ON THE GAS RISER |
| | DRAWING THAT ARE ILLEGIBLE. SUBMIT A CLEAR AND LEGIBLE |
| | SHEET THAT REFLECTS THE SCOPE OF WORK BEING DONE. WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 7- REGULATORS SHALL HAVE A UNION INSTALLED WITHIN 1 |
| | FOOT OF EITHER SIDE OF THE REGULATOR FBC FG 410.2 |
| | |
| | 8-FUTURE POOL HEATER AND FIRE BOWL SHALL HAVE A GAS |
| | SHUT OFF VALVE, GAS REGULATOR, HARD CAP, AND A UNION |
| | INSTALLED WITHIN ONE FOOT OF THE REGULATOR. FBC FG |
| | 410.2 |
| | |
| | 9-SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GAS DRYER. THE GAS DRYER SHALL BE LISTED AND LABELED |
| | PER THE 2017 FBC FUEL GAS SEC.301.3 OR 2017 FBC FUEL |
| | GAS RES. SEC. G2404.3. THE MANUFACTURER'S |
| | SPECIFICATIONS SHALL NOTE THE CFM'S THAT ARE BEING |
| | EXHAUSTED BY THE DRYER. |
| | |
| | 10- PLEASE INDICATE THE EDH OF THE CSST ON THE GAS |
| | ISOMETRIC |
| | |
| | 11-SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE |
| | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC |
| | SEC.304.9.3 OR 2017 FBC R G2407.9.3. COMBINED |
| | COMBUSTION AIR AND VENTILATION AIR SYSTEM |
| | |
| | 12-SUBMIT A COPY OF A HOUSE PLAN SHOWING THE LOCATION |
| | OF THE TANKLESS WATER HEATER AND THE LOCATION AND |
| | DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| | TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| | SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND DRAWN. WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 13- WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |