| Plan Review Notes For Permit 20031254 |
| Permit Number |
20031254 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-04-15 09:01:35 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE COMPLETE PRODUCT APPROVAL. (FRONT | | | PAGES ARE MISSING FROM THE ONE PROVIDED). | | | 2) PLEASE SHOW THE ROOF HEIGHT. | | | 3) PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | THE ZONE 2 AND 3 HIGHER PRESSURES THAN THE MAXIMUM | | | PRESSURE SHOWN ON THE PRODUCT APPROVAL.(SEE GENERAL | | | NOTE NUMBER 9 ON THE PRODUCT APPROVAL PROVIDED) | | | ENGINEERING WILL NEED TO BE SIGNED ELECTRONICALLY FOR | | | USE IN ELECTRONIC PLAN REVIEW. | | | |
|