2020-03-30 14:08:151. A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
 2. PLANS DO NOT DIFFERENTIATE EXISTING VS NEW FIRE AND
 LIFE SAFETY PLANS. NO LIFE SAFETY PLANS INCLUDED.
 UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
 3. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
 4. PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
 5. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 6. ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
 7. PER NFPA 241 SECTION 8.6.2 TEMPORARY SEPARATION
 WALLS: PROTECTION SHALL BE PROVIDED TO SEPARATE AN
 OCCUPIED PORTION OF THE STRUCTURE FROM A PORTION OF THE
 STRUCTURE UNDERGOING ALTERATION, CONSTRUCTION, OR
 DEMOLITION OPERATIONS WHEN SUCH OPERATIONS ARE
 CONSIDERED AS HAVING A HIGHER LEVEL OF HAZARD THAN THE
 OCCUPIED PORTION OF THE BUILDING. WALLS SHALL HAVE AT
 LEAST A 1-HOUR FIRE RESISTANCE RATING. OPENING
 PROTECTIVES SHALL HAVE AT LEAST A 45-MINUTE FIRE
 PROTECTION RATING. NONRATED WALLS AND OPENING
 PROTECTIVES SHALL BE PERMITTED WHEN AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM IS INSTALLED.
  