| 2020-03-30 11:10:53 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1) SHOW THE LOCATION OF THE METER AND DISCONNECT ON THE |
| | ELECTRICAL FLOOR PLANS. FBC 107.2.1 |
| | |
| | 2) PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| | NEW INSTALLATIONS, OR PROVIDE A NOTE REQUIRING |
| | COMPLIANCE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| | |
| | 3) IF ONLY ONE GFCI RECEPTACLE IS TO BE PROVIDE IN THE |
| | MASTER BATH, IT WILL HAVE TO BE CENTERED BETWEEN THE |
| | TWO BASINS. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 |
| | AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| | THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR |
| | PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN |
| | COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON |
| | THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE E3901.6 |
| | |
| | 4) SPECIFY THE REQUIRED EQUIPMENT GROUNDING CONDUCTOR |
| | IN THE PANEL FEEDER RACEWAY SIZED IN ACCORDANCE WITH |
| | FBCR-E3908.12, NEC 250.122 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |