| 2020-03-31 15:51:53 | 03/31/2020 TALKED TO JAMES SHEPARD (CONTRACTOR). HE |
| | SAID HE NEEDS O USE A FULLY BONDED ASSEMBLY BECAUSE OF |
| | EXPOSED CEILING APPEARANCE. TOLD HIM THAT NEED ANOTHER |
| | PRODUCT APPROVAL WITH FULLY BONDED ASSEMBLY THAT MEETS |
| | THE DESIGN PRESSURE FOR ALL ROOF ZONES OR SELECT A |
| | MECHANICALLY FASTENED ASSEMBLY WITH RAS 117 |
| | CALCULATIONS FOR SHORTER NAILS. |
| | |
| | |
| | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL10497-R6 |
| | SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS |
| | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: |
| | IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | RESPONSE: |
| | JAMES SHEPARD LEFT ME A MESSAGE STATING THAT HE'S |
| | INSTALLING ASSEMBLY W-1. THIS IS A BONDED INSULATION |
| | AND BONDED ROOF COVER ASSEMBLY. THE MAXIMUM DESIGN |
| | PRESSURE FOR THIS ASSEMBLY IS -52.5. THIS ASSEMBLY CAN |
| | NOT BE USED BECAUSE IT DOESN'T MEET THE DESIGN PRESSURE |
| | FOR ALL ROOF ZONES AND NOT RATIONAL ANALYSIS IS ALLOWED |
| | FOR FULLY BONDED ASSEMBLIES. SEE LIMITATION #5.8 ON |
| | PAGE 4 OF 5 OF PRODUCT APPROVAL SUBMITTED. |
| | NEED TO SELECT ANOTHER ASSEMBLY THAT MEETS THE DESIGN |
| | PRESSURE FOR ALL ROOF ZONES OR THAT ALLOWS RATIONAL |
| | ANALYSIS (USUALLY RAS 117 CALCULATIONS). |
| | |
| | 2- PROVIDE COMPLETE FLAT ROOF FLORIDA PRODUCT APPROVAL. |
| | PRODUCT APPROVAL SUBMITTED IS MISSING THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE. THIS PAGE IS REQUIRED |
| | BECAUSE IT SHOWS THE CURRENT CODE VERSION AND THE |
| | PRODUCT APPROVAL STATUS. CHAPTER 553 F.S. AND FAC |
| | 61G20-3.001. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |