| 2020-07-20 10:47:32 | 5TH REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT #20031229 |
| | 7/20/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE PREVIOUS REVIEWS LISTED BELOW HAVE |
| | NOT BEEN ADDRESSED ON THE PLANS AND NO NARRATIVE |
| | RESPONSE WAS PROVIDED. |
| | ON THE DATE OF THIS REVIEW- 7/20/17- I CONTACTED THE |
| | COMPANY BY TELEPHONE, AND THE COMPANY HAS AGREED TO |
| | PROVIDE THE CORRECTIONS ON THE NEXT SUBMITTAL. |
| | |
| | 1) THE SUBMITTED GAS RISER DRAWING BY C & C DIVERSIFIED |
| | SERVICES WAS ORIGINALLY SUBMITTED UNDER PERMIT 19040921 |
| | WHICH IS STILL AN OPEN PERMIT. TO DATE NO GAS |
| | INSPECTIONS HAVE BEEN PERFORMED UNDER THAT PERMIT. IF C |
| | & C DIVERSIFIED SERVICES TO BE THE SUB-CONTRACTOR UNDER |
| | THIS GENERATOR PERMIT, THEN A NEW SUB-PERMIT IS |
| | REQUIRED. IF MITCHELL MECHANICAL & ELECTRICAL REMAINS |
| | THE SUB THEN A NEW GAS RISER PLAN SHALL BE SUBMITTED |
| | AND SIGNED BY MITCHELL MECHANICAL AND ELECTRICAL- |
| | SECTIONS 105.3 AND 107.2.1 WPB. |
| | |
| | 2) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED |
| | GENERATOR SPECS INDICATE THE GENERATOR HAS A GAS LOAD |
| | OF 1,202,000 BTUH AT 100% CAPACITY. PLEASE CORRECT THE |
| | LOAD ON THE NEW RISER DRAWING- SECTION 107.2.1 WPB. |
| | |
| | 3) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED RISER |
| | DRAWING SHOWS A NEW REGULATOR FOR THE INTERIOR |
| | GAS-FIRED APPLIANCES WITH A GAS LOAD ESTIMATED AT |
| | 150,000 BTUH. THE NEW RISER SHALL SHOW THE LENGTH OF |
| | THE SYSTEM FROM THE REGULATOR TO THE MOST REMOTE |
| | APPLIANCE- SECTION G2413.4.1 FBC RES; SHOW THE DIAMETER |
| | OF THE NEW 3' PIPE FROM THE METER TO THE REGULATOR, AND |
| | INDICATE THE SIZING TABLE USED FOR THE SYSTEM- SECTION |
| | 2413.3 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |