| 2020-06-04 12:24:05 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT #20031229 |
| | 6/4/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENT #1 FROMTHE 1ST REVIEW PRINTED BELOW WAS NOT |
| | ADDRESSED- PLEASE COMPLY. |
| | |
| | 1) THE NEW GAS ISOMETRIC DRAWING SHOWS TWO INTERIOR |
| | TANKLESS WATER HEATERS THAT ARE NOT LABELED AS EXISTING |
| | ON THE DRAWING. IT APPEARS THESE WILL BE NEW |
| | INSTALLATIONS. PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION GUIDELINES FOR THE |
| | UNITS- SEE SECTIONS P2801.3 AND G2408.1 FBC RES. PLEASE |
| | NOTE THAT A PLUMBING SUB-PERMIT MUST BE SUBMITTED- |
| | SECTION 105.3 WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |