| | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT #20031229 |
| | 5/20/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: |
| | A) INDICATE THE TOTAL BTUH LOAD OF THE ENTIRE SYSTEM |
| | INCLUDING THE EXISTING, NEW, AND FUTURE GAS APPLIANCES |
| | AND EQUIPMENT- SECTIONS 2412.4, 2412.8, 2413.2, & |
| | 2413.3 FBC RES. PLEASE NOTE THAT THE GENERATOR SPECS |
| | INDICATE THE GENERATOR HAS A GAS LOAD OF 1,202,000 BTUH |
| | AT 100% CAPACITY. |
| | B) INDICATE THE TOTAL DEVELOPED LENGTH OF THE GAS |
| | PIPING SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET. |
| | THIS INCLUDES THE EXISTING AND THE NEW PIPING- |
| | SECTIONS- G2413.4.1 & G2413.4.2 FBC RES. A THOROUGH |
| | REVIEW OF THE PIPE SIZING CANNOT BE ACCOMPLISHED |
| | WITHOUT THE TOTAL DEVELOPED LENGTH OF THE SYSTEM- |
| | SECTION 107.2.1 WPB. |
| | C) THE SUBMITTED SPECS FOR THE B31 REGULATORS DO NOT |
| | PROVIDE PERFORMANCE DATA IN LBS. PLEASE INDICATE THE |
| | STEP-DOWN PRESSURES IN PSI OR INCHES W.C. INDICATE THE |
| | MODEL NUMBERS OF THE REGULATORS AND ORIFICE SIZES ON |
| | THE RISER, AND ALSO MARK OR HIGHLIGHT IN THE SPECS THE |
| | MODEL NUMBER AND ORIFICE SIZES AS SHOWN IN THE |
| | PERFORMANCE DATA TABLES- SECTION G2421.1 FBC RES. |
| | D) SHOW THE SHUT OFF VALVE LOCATIONS AT THE METER, AND |
| | AT THE STEP-DOWN REGULATORS- SECTION 2420.1 FBC RES. |
| | E) NOTE: WHERE CONNECTED TO RIGID PIPING, A UNION SHALL |
| | BE INSTALLED WITH 1 FT OF EITHER SIDE OF AN MP |
| | REGULATOR- SECTION G2421.2 FBC RES. |
| | |
| | 2) GAS WATER HEATERS: |
| | A) PROVIDE A BASIC FLOOR PLAN DRAWING SHOWING THE |
| | INSTALLATION LOCATIONS OF THE NEW TANKLESS WATER |
| | HEATERS- SECTION 107.2.1 WPB. |
| | B) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS- SECTION G2408.1 FBC RES. |
| | C) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE |
| | WATER HEATERS AND PROVIDE CALCULATIONS- SECTION G2407.1 |
| | FBC RES. |
| | D) PROVIDE GAS VENTING DIAGRAMS SHOWING THE TYPES AND |
| | SIZES OF VENTS, VENT RUNS THROUGH AND OUT OF THE |
| | BUILDING, TERMINATION LOCATIONS, HEIGHTS ABOVE THE |
| | ROOF, AND ANCHORING DETAILS. SUBMIT SPECIFICATIONS FOR |
| | ALL THE VENT FLUES, CONNECTORS, AND TERMINATION CAPS- |
| | SECTIONS 2426.1 THROUGH 2426.7 FBC RES. |
| | |
| | 3) SURVEY: THE GENERATOR SHALL BE LOCATED AT A MINIMUM |
| | OF 5' FROM THE ADJACENT EXTERIOR WALL, OR VERIFY THE |
| | WALL HAS A 1-HR. FIRE RESISTANCE RATING- SECTION 4.1.4 |
| | (1) NFPA 54. A) INDICATE A MINIMUM 10' CLEARANCE FROM |
| | THE GENERATOR TO AIR INTAKES AND OPERABLE OPENINGS INTO |
| | THE BUILDING WILL BE MAINTAINED PER SECTION R303.5.1 |
| | FBC RES. C) TWO GENERATORS ARE SHOWN ON THE GAS RISER. |
| | SHOW THE LOCATION OF THE FUTURE GENERATOR- SECTION |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |