| Plan Review Notes For Permit 20031229 |
| Permit Number |
20031229 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-05-01 16:33:29 | GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE SIGNED AND SEALED TIEDOWN DETAILS | | | FROM AN ARCHITECT OR ENGINEER TO COMPLY WITH WIND LOADS | | | PER FBC R301.2.1 | | | 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED PER FBC | | | R301.2.1.1 | | | |
|