| 2020-04-01 16:05:08 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) NO ELECTRICAL PLANS SUBMITTED. |
| | |
| | 2) RISER DIAGRAM REQUIRED FOR SERVICE PROVIDE RISER |
| | DIAGRAM OF EXISTING SERVICE. NEC 215.5; FBC 107.2.1 |
| | |
| | 3) PROVIDE LOAD CALCULATION. PROVIDE ACCURATE LOAD |
| | CALCULATION INCLUDING ALL LOADS. NEC 220; FBC RE3602.3 |
| | |
| | 4) HAVE NO IDEA WHAT SIZE GENERATOR IS BEING INSTALLED, |
| | TRANSFER SWITCH (SE RATED OR NOT). |
| | |
| | 5) DEPENDING ON THE SIZE OF THE GENERATOR AND TRANSFER |
| | SWITCH VALUE MAY BE A QUESTION (YOU CAN INCLUDE |
| | CONTRACT ON RESUBMITAL IF YOU LIKE.) |
| | |
| | 6) SUMITTED PLANS SHALL BE SIGNED BY THE ELECTRICAL |
| | QUALIFIER. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY |
| | A DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR |
| | QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | |