| Plan Review Notes For Permit 20031189 |
| Permit Number |
20031189 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-31 08:36:11 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1) SHOW COMPLIANCE WITH FBCR - E 4204.2 FOR | | | EQUIPOTENTIAL BONDING. | | | | | | 2) THE FEEDERS FROM THE BUILDING ELECTRICAL PANEL TO | | | THE 125 AMP POOL PANEL ARE UNDERSIZED. NEC 310.15 | | | | | | NOTE: SEPARATE PERMIT IS REQUIRED FOR THE ELECTRICAL | | | SERVICE CHANGE. | | | | | | END OF COMMENTS. | | | | | | SINCERELY, | | | | | | ROBERT MCDOUGAL | | | COMBINATION PLANS EXAMINER | | | 561-805-6714 | | | [email protected] | | | |
|