Plan Review Notes
Plan Review Notes For Permit 20031160
Permit Number 20031160
Review Stop P
Sequence Number 2
Notes
Date Text
2020-06-24 11:54:142ND REVIEW FBC-2017 PLUMBING
 PERMIT #20031160
 6/24/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EFFICIENCY RATING OF THE WATER HEATER IS NOTED AT
 .93 ON SHEET S-1, BUT THE ENERGY COMPLIANCE FORM
 INDICATES .95.
  
 2) S1 & A1: THE WATER HEATER PAN DRAIN LINE MUST
 TERMINATE NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE
 THAN 24 INCHES (610 MM) ABOVE THE ADJACENT GROUND
 SURFACE - SECTION P2801.6.2 FBC P. THE PLAN APPEARS TO
 SHOW THE LINE RUNNING UNDER THE SLAB WHICH WOULD RESULT
 IN A BELOW GRADE TERMINATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  