| Plan Review Notes For Permit 20031160 |
| Permit Number |
20031160 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-06-30 13:18:33 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PRODUCT APPROVALS FOR THE PLASTPRO DOORS DO NOT SHOW | | | AN ATTACHMENT ANCHOR TYPE TO METAL FRAME. PLEASE SHOW | | | ON THE DRAWINGS THE ANCHORS TO USE FOR THE FASTENING OF | | | THE PLASTPRO DOORS. | | | 2) MASONITE DOOR PROVIDED DOES NOT APPEAR TO HAVE AN | | | APPROVED MIAMI DADE OR FLORIDA STATE PRODUCT APPROVAL. | | | 3) ROOFING PRODUCT APPROVAL = ROOFING SYSTEM MARKED ON | | | THE PRODUCT APPROVAL SHOWS A MAX. WIND DESIGN PRESSURE | | | OF (-52.5) - PLEASE SEE NOTE NUMBER 7 ON THE PRODUCT | | | APPROVAL AND PROVIDE SIGNED AND SEALED ADDITIONAL | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | ZONES 2 AND 3 THAT MAY BE HIGHER WIND PRESSURE THAN THE | | | MAX. SHOWN ON THE PRODUCT APPROVAL. | | | 4) PLEASE SHOW HOW THE 1 5/8 INCH METAL STUDS ARE | | | FASTENED TO THE METAL BUILDING (TYPE, SIZE AND ON | | | CENTER SPACING OF FASTENERS). TO COMPLY WITH THE WIND | | | LOADS PER FBC 1609 | | | 5) SHOW HOW THE LATH IS FASTENED TO THE METAL SDUDS | | | ETC. TO COMPLY WITH THE WIND LOADS FBC 1609 |
|