Plan Review Notes
Plan Review Notes For Permit 20031160
Permit Number 20031160
Review Stop P
Sequence Number 1
Notes
Date Text
2020-04-14 17:16:101ST REVIEW FBC-2017 PLUMBING
 PERMIT #20031160
 4/14/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET S1: CORRECT PLUMBING NOTE #4- POLYBUTYL IS NOT
 AN APPROVED DOMESTIC WATER SERVICE OR DISTRIBUTION
 PIPING MATERIAL- SECTIONS P2906.4 & 2906.5 FBC RES.
  
 2) S1: CORRECT PLUMBING NOTE #4- CPVC IS NOT AN
 APPROVED SANITARY PIPING MATERIAL- SECTION P3002.1 FBC
 RES.
  
 3) S1: CORRECT NOTE #16- SHOWER VALVES SHALL BE OF THE
 PRESSURE BALANCED, THERMOSTATIC-MIXING, OR COMBINATION
 PRESSURE BALANCE/THERMOSTATIC MIXING VALVE TYPES WITH A
 HIGH LIMIT STOP IN ACCORDANCE WITH ASSE A112.106/CSA
 B125.16- SECTION 2708.4 FBC RES.
  
 4) S1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE ELECTRIC
 WATER HEATER THAT INCLUDES THE EFFICIENCY RATING OF THE
 UNIT- TABLE C404.2 FBC EC. PLEASE NOTE THAN AN ENERGY
 COMPLIANCE FORM WAS NOT SUBMITTED- SEE SECTION R101.1.5
 FBC RES.
  
 5) S1 & A1: THE WATER HEATER DETAIL ON S1 SHOWS THE
 RELIEF VALVE PIPE DISCHARGING TO A FLOOR DRAIN, AND A
 OVERFLOW LINE FROM THE DRAIN PAN RUNNING TO THE
 EXTERIOR OF THE BUILDING. PLEASE SHOW THE FLOOR DRAIN
 AND DRAIN LINE RUN ON SHEET A1.
  
 6) A1: ROOM DIMENSIONS AND REQUIRED FIXTURE CLEARANCES
 NOT PROVIDED IN THE BATHROOMS-SECTION 107.2.1 WPB &
 SECTION R307.1 FBC RES.
  
 7) S1 PLUMBING RISER: A) SHOW TWO KS TRAPS. B) SHOW THE
 SIZE OF THE WM STANDPIPE AND TRAP, THE WASTE STACK, AND
 THE VENT- TABLE P3201 FBC RES, SECTION 406.2 FBC P, AND
 TABLE 709.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  