| 2020-04-14 17:16:10 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT #20031160 |
| | 4/14/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET S1: CORRECT PLUMBING NOTE #4- POLYBUTYL IS NOT |
| | AN APPROVED DOMESTIC WATER SERVICE OR DISTRIBUTION |
| | PIPING MATERIAL- SECTIONS P2906.4 & 2906.5 FBC RES. |
| | |
| | 2) S1: CORRECT PLUMBING NOTE #4- CPVC IS NOT AN |
| | APPROVED SANITARY PIPING MATERIAL- SECTION P3002.1 FBC |
| | RES. |
| | |
| | 3) S1: CORRECT NOTE #16- SHOWER VALVES SHALL BE OF THE |
| | PRESSURE BALANCED, THERMOSTATIC-MIXING, OR COMBINATION |
| | PRESSURE BALANCE/THERMOSTATIC MIXING VALVE TYPES WITH A |
| | HIGH LIMIT STOP IN ACCORDANCE WITH ASSE A112.106/CSA |
| | B125.16- SECTION 2708.4 FBC RES. |
| | |
| | 4) S1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE ELECTRIC |
| | WATER HEATER THAT INCLUDES THE EFFICIENCY RATING OF THE |
| | UNIT- TABLE C404.2 FBC EC. PLEASE NOTE THAN AN ENERGY |
| | COMPLIANCE FORM WAS NOT SUBMITTED- SEE SECTION R101.1.5 |
| | FBC RES. |
| | |
| | 5) S1 & A1: THE WATER HEATER DETAIL ON S1 SHOWS THE |
| | RELIEF VALVE PIPE DISCHARGING TO A FLOOR DRAIN, AND A |
| | OVERFLOW LINE FROM THE DRAIN PAN RUNNING TO THE |
| | EXTERIOR OF THE BUILDING. PLEASE SHOW THE FLOOR DRAIN |
| | AND DRAIN LINE RUN ON SHEET A1. |
| | |
| | 6) A1: ROOM DIMENSIONS AND REQUIRED FIXTURE CLEARANCES |
| | NOT PROVIDED IN THE BATHROOMS-SECTION 107.2.1 WPB & |
| | SECTION R307.1 FBC RES. |
| | |
| | 7) S1 PLUMBING RISER: A) SHOW TWO KS TRAPS. B) SHOW THE |
| | SIZE OF THE WM STANDPIPE AND TRAP, THE WASTE STACK, AND |
| | THE VENT- TABLE P3201 FBC RES, SECTION 406.2 FBC P, AND |
| | TABLE 709.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |