2020-04-23 07:42:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM IS NOT CODE COMPLIANT. SERVICE
 CONDUCTORS ARE NOT PERMITTED TO EXTEND FURTHER THAN 8
 FEET INTO A STRUCTURE WITHOUT OVERCURRENT PROTECTION.
 IF THIS OVERCURRENT PROTECTION IS LOCATED ON THE
 EXTERIOR OF THE DWELLING, THAN THE CONDUIT TO THE
 INTERIOR PANEL MUST INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. RISER SHOWS WHAT APPEARS TO BE A METER CAN
 ONLY LABELED AS A METER MAIN DISCONNECT OUTSIDE, BUT
 ALSO SHOWS A MAIN BREAKER PANEL INSIDE. IF THE
 CONDUCTORS ARE RUN UNDERGROUND FROM THE METER TO THE
 INTERIOR PANEL, AND THAT PANEL HAS A MAIN BREAKER, THE
 CONDUCTORS MUST NOT EXCEED 8 FEET IN LENGTH BEFORE
 TERMINATION TO THE MAIN BREAKER. PROVIDE CLARIFICATION
 AND/OR CORRECTION. NEC 230.70, 250.122; FBC RE E3601.6,
 E3704.6, 3607.3.1
 2. AFCI PROTECTION SHOWN IN NOTE 21 IS NOT CODE
 COMPLIANT. THIS NOTE ONLY REQUIRES RECEPTACLES TO BE
 AFCI PROTECTED. ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. THIS INCLUDES LIGHTING AND POWER OUTLETS AND
 RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI AND GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12; FBC
 RE E3902
 3. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 4. FAULT CURRENT CALCULATION IS INCORRECT. THIS IS NOT
 A PARALLEL SERVICE, SO THERE WOULD NOT BE 2 CONDUCTORS
 PER PHASE. ALSO, RISER DIAGRAM DOES NOT SHOW THE WIRE
 FROM THE FPL TRANSFORMER TO THE METER MAIN DISCONNECT,
 SO HOW WAS THIS CALCULATION PERFORMED? WHAT WIRE SIZE
 WAS USED? PROVIDE CORRECTED CALCULATION. NEC 110.9,
 110.10; FBC RE E3606.3
 5. RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. THE
 WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER SPACE
 STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THIS INCLUDES ANY WALL SPACE 2 FEET OR
 MORE IN WIDTH. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE E3901
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER