2020-04-21 10:37:43NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ATTACHMENT TO FOUNDATION = DRAWING S1 SHOWS 2-#5'S 8
 INCH LONG BOLTS - DRAWING A-2 SHOWS 2-12 INCH LONG
 DOWELS. PLEASE CLARIFY (BOLTS OR DOWELS? DOWELS WHAT
 DIAMETER? 8" OR 12" LONG?).
 2) PLEASE SHOW THE THICKNESS OF THE CONCRETE PATIO
 SLABS.
 3) PLEASE SHOW ALL ATTACHMENTS (TYPE, DIAMETER, LENGTH
 AND ON CENTER SPACING = WALL SHEATHING TO METAL
 FRAMING, LATH TO METAL FRAMING, STRAPPING NAIL
 REQUIREMENTS, HUC 28 HANGER TO METAL CONTAINER, PARAPET
 WALL SILL PLATE BOLT ON CENTER SPACING ETC.
 4) PRODUCT APPROVALS FOR THE DOORS AND WINDOWS DO NOT
 SHOW AN ATTACHMENT ANCHOR TYPE TO METAL.
 5) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT.
 (ELECTRONICALLY SIGNED FOR USE IN ELECTRONIC PLAN
 REVIEW).
 6) INSULATION SHOWN FOR WALLS AND CEILINGS NEEDS TO
 MATCH OR EXCEED WHAT IS SHOWN ON THE ENERGY CALCS. (
 ENERGY CALCS. NOT YET PROVIDED)
 7) PLEASE SHOW ROOF CLADDING PRESSURES FOR WIND ZONES
 1,2 AND 3.
 8) ROOFING PRODUCT APPROVAL = ROOFING SYSTEM MARKED ON
 THE PRODUCT APPROVAL SHOWS A MAX. WIND DESIGN PRESSURE
 OF (-52.5) - PLEASE SEE NOTE NUMBER 7 ON THE PRODUCT
 APPROVAL AND PROVIDE SIGNED AND SEALED ADDITIONAL
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ZONES 2 AND 3 THAT MAY BE HIGHER WIND PRESSURE THAN THE
 MAX. SHOWN ON THE PRODUCT APPROVAL.
  