| 2020-04-17 12:38:38 | |
| | 1ST REVIEW FBC-2017 PLUMBING/FUEL GAS |
| | PERMIT #20031112 |
| | 4/17/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE UNDERGROUND PE PIPING RUNS ON THE SITE PLAN AND |
| | ISOMETRIC DRAWINGS DO NOT MATCH. THE ISO SHOWS A ?? PE |
| | BRANCH LINE TO THE POOL HEATER TEEING OFF FROM THE ?? |
| | MAIN AT 40? UPSTREAM OF THE TANK. THE SITE PLAN SHOWS A |
| | STRAIGHT 100? 1/2? PE RUN TO THE POOL HEATER. REVISE |
| | THE DRAWINGS SO THEY MATCH- SECTION 107.2.1 WPB. |
| | |
| | 2) IT APPEARS THAT UNDER THE POOL PERMIT #19090743, THE |
| | EXISTING GAS LINE WAS POSSIBLY REMOVED OR RELOCATED |
| | DURING POOL CONSTRUCTION. ON THE SITE PLAN OR ISOMETRIC |
| | DRAWING, INDICATE THE BURIAL DEPTH OF THE PIPE AND TYPE |
| | OF SLEEVING USED UNDER THE PAVER DECK- SECTION G2415.12 |
| | FBC RES |
| | |
| | 3) MODIFY THE ISOMETRIC DRAWING TO INDICATE: |
| | A) THE DELIVERY PRESSURES AT THE 2ND STAGE REGULATORS- |
| | G2413.2 & G2413.4.3 |
| | B) TOTAL BTUH LOAD ON THE SYSTEM- G2413.3. |
| | C) THE TYPE AND SIZE OF PIPING, AND THE LENGTHS OF THE |
| | PIPING RUNS FROM THE REGULATORS TO THE HEATER AND |
| | GRILL- G2413.3 & G2413.4 |
| | D) LOCATIONS OF REQUIRED PIPE UNIONS AND THE 2ND STAGE |
| | REGULATOR- G2421.2 |
| | E) LOCATIONS OF SHUTOFF VALVES AT THE HEATER AND GRILL- |
| | G2420.5. |
| | F) INDICATE WHICH PIPE SIZING TABLES WERE USED FOR THE |
| | PE AND THE 2ND STAGE PIPING- TABLES G2413.4.1- G2413.2. |
| | |
| | 4) PLEASE LIST THE MAKE AND MODEL NUMBER OF THE POOL |
| | HEATER ON THE ISOMETRIC DRAWING- SECTION 107.2.1 WPB. |
| | |
| | 5) THE COST OF THE POOL HEATER SHALL BE INCLUDED IN THE |
| | TOTAL VALUE OF THE PERMIT. PERMIT VALUE INCLUDES THE |
| | TOTAL COST OF LABOR, MATERIALS, EQUIPMENT AND |
| | APPLIANCES, SITE WORK, AND DESIGN FEES- SECTION 109.3 |
| | WPB |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | |
| | |