| Plan Review Notes For Permit 20031112 |
| Permit Number |
20031112 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-24 15:36:09 | 1. FBC 107.2.1 PROVIDE COMPLETE INSTALLATION PLAN | | | DRAWING FOR CONNECTION OF GAS TO POOL WATER HEATER, | | | INCLUDING GAS RISER DIAGRAM WITH LEGIBLE PRINTING, | | | INCLUDING ANY OTHER EXISTING APPLIANCES AND BTUH | | | VALUES, PIPE SIZING CRITERIA, WHERE EXISTING IS | | | LOCATED, EXISTING PIPING ON PLAN, HOW IT IS TO BE RE | | | ROUTED, PIPING MATERIALS AND VALVING. IT APPEARS A BBQ | | | IS BEING REMOVED? | | | 2. FBC 107.2.1 POOL HEATER BROCHURE IS INADEQUATE IN | | | THAT THE SIZE, MODEL OR ANY OTHER INFORMATION IS GIVEN. | | | 3. FBC FUEL GAS SECTION 404. PLEASE NOT THAT PIPING IN | | | CONCEALED LOCATIONS SHALL NOT HAVE UNIONS, TUBING | | | FITTINGS, RIGHT AND LEFT COUPLINGS, BUSHINGS, | | | COMPRESSION COUPLINGS AND SWING JOINTS MADE BY | | | COMBINATIONS OF FITTINGS UNLESS THE FITTINGS ARE LISTED | | | FOR USE IN CONCEALED LOCATIONS. | | | 4. FBC 107.2.1 PROVIDE DETAILS OF POOL HEATER | | | INSTALLATION INCLUDING APPROVED HURRICANE TIEDOWNS FOR | | | THE HEATER. | | | | | | REVIEWED REMOTELY BY JAMES BAKER, PE | | | PX3997, PE77268 | | | 561-805-6724 | | | [email protected] | | | | | | |
|