| 2020-03-30 10:36:20 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | 1) PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | |
| | 2) PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE |
| | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24. |
| | |
| | 3) PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC CE R404.1 |
| | |
| | 4) ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS, |
| | LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING |
| | ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC |
| | RE3902.16 LAUNDRY AREA |
| | |
| | 5) E3902.9 LAUNDRY AREAS. 125-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE RECEPTACLES INSTALLED IN LAUNDRY AREAS |
| | SHALL HAVE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION |
| | FOR PERSONNEL. [210.8(A)(9)] |
| | |
| | 6) E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT. |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE |
| | PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN |
| | DWELLING UNIT LOCATIONS. [210.8(D)] |
| | |
| | 7) SHOW LOCATION OF SERVICE AND PANELS NO LOCATION |
| | SHOWN. E3601.6.2 SERVICE DISCONNECT LOCATION. |
| | |
| | 8) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. NEC |
| | 210.52(E)(1) FBC RE3901.7 |
| | |
| | 9) STORAGE OUTLET TO BE GFCI PROTECTED |
| | |
| | 10) NO LOW VOLTAGE WIRING SHOWN ON PLANS THIS IS NOT |
| | REQUIREMENT BUT MAY DELAY JOB FOR A REVISION IN FIELD. |
| | |
| | 11) PANEL SCHEDULE DOE NOT INCLUDE THE WATER HEATER |