| Plan Review Notes For Permit 20031096 |
| Permit Number |
20031096 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-08-17 10:12:49 | REVISION - GATE AND SHUTTER | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ROLLUP SHUTTER - CANNOT BE USED AS A DOOR - UNLESS | | | IT CAN BE UNLATCHED OR UNLOCKED FROM THE INSIDE (EGRESS | | | SIDE) FBC 1010.1.9 | | | 2) PLEASE SHOW THE GATE DOOR LOCKING HARDWARE TO COMPLY | | | WITH FBC 1010.1.9 | | | 3) THE SHOP DRAWINGS FOR THE GATE DOOR DO NOT SHOW IN | | | "ADOBE READER" AS ELECTRONICALLY/DIGITALLY SIGNED - | | | PLEASE TRY UPLOADING (F1 AND F2) A SECOND TIME WITHOUT | | | THE APPROVAL STAMPS. (ELECTRONICALLY SIGNED DRAWINGS | | | AND DOCUMENTS CANNOT BE PRINTED OUT THEY WILL LOSE | | | THEIR ELECTRONIC SIGNATURE) |
|