| 2020-03-26 08:34:08 | |
| | |
| | REVISION BUILDING REVIEW COMMENTS. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- THE REVISION IS TO CHANGE DOOR TO ROLL DOWN |
| | HURRICANE SHUTTERS. THIS WAS DISCUSSED WITH ROBERT |
| | BROWN AND AND DYLAN BATTLES. SHUTTERS ARE OK BUT EGRESS |
| | NEEDS TO BE CLARIFIED. PROVIDE SPECIFICATIONS SHOWING |
| | HOW THE SHUTTERS ARE OPERABLE FROM THE INSIDE TO ALLOW |
| | EGRESS IN CASE THE SHUTTERS ARE CLOSED DOWN. SEC. |
| | 1001.1 FBC-BUILDING. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- THIS IS A REVISION TO THE ALREADY APPROVED DOOR |
| | PRODUCT APPROVAL NOA 18-0301.08. |
| | PRODUCT APPROVAL SUBMITTED NOW IS FOR ROLL UP HURRICANE |
| | SHUTTERS NOT FOR A DOOR. NEED TO PROVIDE COMPLETE |
| | HURRICANE SHUTTERS INSTALLATION SCHEDULE AS REQUIRED BY |
| | CITY POLICY FOR ALL HURRICANE SHUTTERS INSTALLATIONS. |
| | SEE HURRICANE SHUTTERS INSTALLATION SCHEDULE SAMPLE OR |
| | PROVIDE COMPLETE INFORMATION IN A DIFFERENT FORMAT THAT |
| | WILL SPECIFY ALL THE REQUIRED INFORMATION. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- CORRECTED MASTER NUMBER REFERENCED IN THE SUBMITTAL. |
| | THE MASTER FOR THE GENERATOR ENCLOSURE IS 19100813 NOT |
| | 19100815. |
| | THIS IS A REVISION TO THE ALREADY APPROVED DOOR PRODUCT |
| | APPROVAL NOT A SUBMITTAL. REVISION FEES APPLY. OWE |
| | $175.25 FOR REVISION FEES. |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | I SPOKE TO ROBERT ABOUT THIS ONE AND HE IS OK WITH THE |
| | ROLLUP SHUTTER BUT IT NEEDS TO BE ABLE TO OPEN FROM THE |
| | INSIDE IF SOMEONE CLOSES IT. |
| | JUST COMMENT ABOUT THAT ASPECT OF IT AND HOW THE |
| | HARDWARE WORKS. |
| | |