 REVISION BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- THE REVISION IS TO CHANGE DOOR TO ROLL DOWN
 HURRICANE SHUTTERS. THIS WAS DISCUSSED WITH ROBERT
 BROWN AND AND DYLAN BATTLES. SHUTTERS ARE OK BUT EGRESS
 NEEDS TO BE CLARIFIED. PROVIDE SPECIFICATIONS SHOWING
 HOW THE SHUTTERS ARE OPERABLE FROM THE INSIDE TO ALLOW
 EGRESS IN CASE THE SHUTTERS ARE CLOSED DOWN. SEC.
 1001.1 FBC-BUILDING. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- THIS IS A REVISION TO THE ALREADY APPROVED DOOR
 PRODUCT APPROVAL NOA 18-0301.08.
 PRODUCT APPROVAL SUBMITTED NOW IS FOR ROLL UP HURRICANE
 SHUTTERS NOT FOR A DOOR. NEED TO PROVIDE COMPLETE
 HURRICANE SHUTTERS INSTALLATION SCHEDULE AS REQUIRED BY
 CITY POLICY FOR ALL HURRICANE SHUTTERS INSTALLATIONS.
 SEE HURRICANE SHUTTERS INSTALLATION SCHEDULE SAMPLE OR
 PROVIDE COMPLETE INFORMATION IN A DIFFERENT FORMAT THAT
 WILL SPECIFY ALL THE REQUIRED INFORMATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- CORRECTED MASTER NUMBER REFERENCED IN THE SUBMITTAL.
 THE MASTER FOR THE GENERATOR ENCLOSURE IS 19100813 NOT
 19100815.
 THIS IS A REVISION TO THE ALREADY APPROVED DOOR PRODUCT
 APPROVAL NOT A SUBMITTAL. REVISION FEES APPLY. OWE
 $175.25 FOR REVISION FEES.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
 I SPOKE TO ROBERT ABOUT THIS ONE AND HE IS OK WITH THE
 ROLLUP SHUTTER BUT IT NEEDS TO BE ABLE TO OPEN FROM THE
 INSIDE IF SOMEONE CLOSES IT.
 JUST COMMENT ABOUT THAT ASPECT OF IT AND HOW THE
 HARDWARE WORKS.
  