| 2020-06-29 13:28:36 | 1) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. |
| | SEC. G 2413.4.1, G2413.4.2. |
| | 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | 3) PLACE A NOTE ON THE PLANS SPECIFYING WHICH SIZING |
| | TABLE(S) FROM THE FUEL GAS CODE THAT WAS USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. FBC-FUEL GAS SECS. 401.4, |
| | 401.8, 402.3. |
| | 4) INDICATE ON THE PLAN THE TYPE OF PIPE BEING |
| | INSTALLED. |
| | 5) SUBMIT A COPY OF THE OPERATION AND INSTALLATION |
| | MANUAL (OIM) AS REFERENCED ON THE PLANS. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 6) SHT. D1 DOES NOT SHOW ANY EXISTING GAS PIPING. |
| | SUBMIT AN EXISTING PIPING PLAN THAT SHOWS ALL EXISTING |
| | GAS PIPING TO BE REMOVED. IDENTIFY ALL NEW GAS PIPING |
| | TO BE INSTALLED AND ANY EXISTING GAS PIPING THAT IS TO |
| | REMAIN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 7) SHT. P-3 - THE PLANS SHOW AN EXISTING FAN LABELED AS |
| | SF-1 (SUPPLY FAN?) TO REMAIN BUT THE PLAN SHOWS A |
| | DIRECTIONAL ARROW INDICATING THIS MAY BE AN EXHAUST |
| | FAN. CLARIFY. |
| | 8) COMBUSTION AIR CALCULATIONS HAVE BEEN SUBMITTED FOR |
| | A MECHANICAL COMBUSTION AIR SUPPLY SYSTEM BUT THERE IS |
| | NO INFORMATION ON THE PLANS AS TO HOW THIS COMBUSTION |
| | AIR IS BEING SUPPLIED. THE PLANS ALSO SHOW COMBUSTION |
| | AIR BEING SUPPLIED BY A LOUVER, NOT BY MECHANICAL |
| | MEANS. CLARIFY. |
| | 9) PROVIDE DETAILS AS TO HOW THE EXHAUST PIPE |
| | PENETRATIONS WILL BE SEALED? ARE ANY OF THESE WALLS |
| | FIRE RATED? IF SO, SUBMIT DETAILS FOR THE LISTED |
| | FIRESTOPPING SYSTEMS TO BE USED. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 10) PROVIDE INFORMATION FOR THE TERMINATION LOCATION OF |
| | THE EXHAUST VENT. THE EXIT TERMINAL OF A MECHANICAL |
| | DRAFT SYSTEM ( IF INSTALLED ) SHALL COMPLY WITH |
| | FBC-FUEL GAS SEC. 503.3.3, (1-6), 503.8 (1) (2). |
| | 11) PROVIDE DETAILS FOR THE EXHAUST SSUPPORTS. SHOW |
| | SUPPORT LOCATIONS, TYPE OF SUPPORTS, SPACING, ETC. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |